Figure 5.12: Mounting of bottom plate,Frame size E1.
The bottom plate of the E1 frame can be mounted from either inside or outside of the enclosure, allowing flexibility in the installation process, i.e., if
mounted from the bottom, the glands and cables can be mounted before the adjustable frequency drive is placed on the pedestal.
5.2.9 IP21 Drip Shield Installation (frame size D1 and D2 )
To comply with the IP21 rating, a separate drip shield is to be
installed as explained below:
•
Remove the two front screws.
•
Insert the drip shield and replace the screws.
•
Torque the screws to 5.6 Nm (50 in-lbs).
Figure 5.13: Install the drip shield.
5 How to Install
VLT
®
AQUA Drive Design Guide
5-14
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark