8.2.11. Timed Actions, 23-0*
Use
Timed Actions
for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up
to 10 Timed Actions can be programmed in the frequency converter. The Timed Action number is selected from the list when entering parameter group
23-0* from the Local Control Panel. par. 23-00
then refer to the selected Timed Action number. Each Timed Action is
divided into an ON time and an OFF time, in which two different actions may be performed.
NB!
The clock (parameter group 0-7*) must be correctly programmed for Timed Actions to function correctly.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-00 ON Time
Array [10]
Range:
Function:
0 N/A*
[0 - 0 N/A]
Sets the ON time for the Timed Action.
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. In par. 0-79 Clock
Fault
it is possible
to program for a Warning in case clock has not been set properly, e.g. after a
power down.
23-01 ON Action
Arra [10]
Option:
Function:
Select the action during ON Time. See par. 13-52 SL
Controller Action
for descriptions of the options.
[0] *
Disabled
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset ref 0
[11]
Select preset ref 1
[12]
Select preset ref 2
[13]
Select preset ref 3
[14]
Select preset ref 4
[15]
Select preset ref 5
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select ramp 1
[19]
Select ramp 2
[22]
Run
8. How to programme the frequency converter
VLT
®
AQUA Drive
Operating Instructions
104
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
8