22-35 Low Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par. 0-03 Regional
Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
0 RPM*
[0 - par. 4-13 RPM]
To be used if par. 0-02 Motor
Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range:
Function:
0.0 Hz*
[0.0 - par. 4-14 Hz]
To be used if par. 0-02 Motor
Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range:
Function:
0 kW*
[0.00 - 0.00 kW]
To be used if par. 0-03 Regional
Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-39 High Speed Power [HP]
Range:
Function:
0 hp*
[0.00 - 0.00 hp]
To be used if par. 0-03 Regional
Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-40 Minimum Run Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum running time for the motor after a Start command (digital input or Bus)
before entering Sleep Mode.
22-41 Minimum Sleep Time
Range:
Function:
10 s*
[0 - 600 s]
Set the desired minimum time for staying in Sleep Mode. This will override any wake up conditions.
22-42 Wake-up Speed [RPM]
Range:
Function:
0 RPM*
[par. 4-11 - par. 4-13 RPM]
To be used if par. 0-02 Motor
Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par. 1-00
is set for Open Loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
99