5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see
also par. 5-58 Term.
33 High Ref./Feedb. Value
.
8.2.8. 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
6-00 Live Zero Timeout Time
Range:
Function:
10 s*
[1 - 99 s]
Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e.
terminal 53 or terminal 54, allocated to current and used as reference or feedback sources. If the
reference signal value associated with the selected current input falls below 50% of the value set
in par. 6-10
, par. 6-12 Terminal
53 Low Current
or par. 6-22 Terminal
54 Low Current
for a time period longer than the time set in par.
, the function selected in par. 6-01
will be
activated.
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set in par. 6-01
will be acti-
vated if the input signal on terminal 53 or 54 is below 50% of the value in par. 6-10
, par. 6-12 Terminal
53 Low Current
or par.
6-22 Terminal
54 Low Current
for a time period defined in par. 6-00
. If
several time-outs occur simultaneously, the frequency converter prioritises the time-out functions
as follows:
1.
2.
par. 8-04 Control
Timeout Function
The output frequency of the frequency converter can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent trip
If you select set-up 1-4, par. 0-10 Active
Set-up
must be set to
Multi Set-up
, [9].
This parameter cannot be adjusted while the motor is running.
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
8. How to programme the frequency converter