[Main Menu]
is used for programming all parameters.
The Main Menu parameters can be accessed immediately unless a password has been created via par. 0-60, 0-61, 0-65 or 0-66. For the majority of water
and wastewater applications it is not necessary to access the Main Menu parameters but instead the Quick Menu, Quick Setup and Function Setups
provides the simplest and quickest access to the typical required parameters.
It is possible to switch directly between Main Menu mode and Quick Menu mode.
Parameter shortcut can be carried out by pressing down the
[Main Menu]
key for 3 seconds. The parameter shortcut allows direct access to any
parameter.
[Alarm Log]
displays an Alarm list of the five latest alarms (numbered A1-A5). To obtain additional details about an alarm, use the arrow keys to manoeuvre to the
alarm number and press [OK]. Information is displayed about the condition of the frequency converter before it enters the alarm mode.
[Back]
reverts to the previous step or layer in the navigation structure.
[Cancel]
last change or command will be cancelled as long as the display has not
been changed.
[Info]
displays information about a command, parameter, or function in any
display window. [Info] provides detailed information when needed.
Exit Info mode by pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between the different
choices available in
[Quick Menu]
,
[Main Menu]
and
[Alarm Log]
.
Use the keys to move the cursor.
[OK]
is used for choosing a parameter marked by the cursor and for enabling
the change of a parameter.
Operation Keys
for local control are found at the bottom of the control panel.
130BP046.10
[Hand On]
enables control of the frequency converter via the GLCP. [Hand on] also starts the motor, and it is now possible to give the motor speed reference by
means of the arrow keys. The key can be
Enabled
[1] or
Disabled
[0] via par.
0-40 [Hand on] Key on LCP.
The following control signals will still be active when [Hand on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse (motor coasting to stop)
7. How to operate the frequency converter
VLT
®
AQUA Drive
Operating Instructions
54