0-12 This Set-up Linked to
Option:
Function:
Set-up 1. A switch between Set-up 1 and Set-up
2 during operation is now possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Range:
Function:
0
*
[0 -
255 ]
View a list of all the set-ups linked by means of
0-12 This Set-up Linked to
. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
set-ups are linked to that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 6.7 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Edit Set-ups / Channel
Range:
Function:
0
*
[-2147483648 -
2147483647]
View the setting of
parameter 0-11 Edit Set-
up
for each of the 4 different
communication channels. When the
number is displayed as a hex number, as it
is in the LCP, each number represents 1
channel.
Numbers 1-4 represent a set-up number; F
means factory setting; and A means active
set-up. The channels are, from right to left:
LCP, FC bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
the following:
•
The frequency converter selected
Set-up 2 via a fieldbus channel.
This selection is reflected in
parameter 0-11 Edit Set-up
.
•
A user selected Set-up 1 via the
LCP.
•
All other channels are using the
active set-up.
6.4.3 0-2* LCP Display
Define the variables displayed in the LCP.
NOTICE
Refer to
0-37 Display Text 1
,
0-38 Display Text 2
and
0-39 Display Text 3
for information on how to write
display texts.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in
line 1, left position.
[0]
None
No display value selected.
[1501]
Running Hours
Running hours meter of the
unit.
[1600]
Control Word
Present control word
[1603]
Status Word
Present status word.
[1630]
DC Link Voltage
Intermediate circuit voltage in
the unit.
[1634]
Heatsink Temp.
Present heat sink temperature
of the unit. The cut-out limit is
95 ±5 °C; cutting back in occurs
at 70 ±5 °C.
[1635]
Inverter Thermal
Percentage load of the inverters.
[1636]
Inv. Nom. Current
Nominal current of the unit.
[1637]
Inv. Max. Current
Maximum current of the unit.
[1639]
Control Card Temp.
Temperature of the control card.
[1660]
Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and
33). There are 16 bits in total,
but only 6 of them are used.
Input 18 corresponds to the
leftmost of the used bits. Signal
low=0; Signal high=1.
[1666]
Digital Output [bin]
Binary value of all digital
outputs.
[1671]
Relay Output [bin]
Binary value of the relay
outputs.
[1680]
Fieldbus CTW 1
Control word (CTW) received
from the bus master.
[1684]
Comm. Option STW
Extended Fieldbus communi-
cation option status word.
[1685]
FC Port CTW 1
Control word (CTW) received
from the bus master.
[1690]
Alarm Word
One or more alarms in a hex
code.
[1691]
Alarm Word 2
One or more alarms in a hex
code.
[1692]
Warning Word
One or more warnings in a hex
code.
[1693]
Warning Word 2
One or more warnings in a hex
code.
[1694]
Ext. Status Word
One or more status conditions
in a hex code.
Applications and Basic Prog...
Operating Instructions
MG90V302
Danfoss A/S © 09/2014 All rights reserved.
43
6
6