14-22 Operation Mode
Option:
Function:
130BA097.12
FC 302
FC 301
FC 301 &
FC 302
13
12
18
37
32
27
19
29
33 20
50
39 42
54
53
55
19
18
12 13
20
33
27
32
Illustration 6.8 Terminal Connections
[2] Initiali-
sation
Select
[2] Initialisation
to reset all parameter
values to default settings, except for
parameter 15-03 Power Up's
,
parameter 15-04 Over Temp's
, and
parameter 15-05 Over Volt's
. The unit resets
during the next power-up.
Parameter 14-22 Operation Mode
also reverts to
the default setting
[0] Normal operation
.
[3] Boot
mode
14-29 Service Code
Range:
Function:
0
*
[-2147483647 - 2147483647]
For internal service only.
14-50 RFI Filter
Option: Function:
[0]
Off Select
[0] Off
only if the unit is fed by an isolated
mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
*
On Select
[1] On
to ensure that the unit complies with
EMC standards.
14-54 Bus Partner
Range:
Function:
1
*
[0 - 126 ]
Applications and Basic Prog...
Operating Instructions
MG90V302
Danfoss A/S © 09/2014 All rights reserved.
51