PCC1
130BB519.11
M
M
AAF
Illustration 4.15 CTs Do Not Measure Capacitor Current
For installations where the CT connection point can be
moved, the configuration shown in
Illustration 4.15
is also
possible. In some retrofit applications, summation CTs are
needed to ensure that the capacitor current is not
measured.
Summation CTs can also be used to subtract 2 signals from
each other and so subtract the capacitor bank corrected
current from the total current.
NOTICE
Use summation CTs with an accuracy of 0.5% of better.
PCC1
130BB520.11
M
M
AAF
Illustration 4.16 Capacitor Bank Mounted on PCC with CTs
Ensuring that Capacitor Corrected Current is not Measured.
Electrical Installation
Operating Instructions
MG90V302
Danfoss A/S © 09/2014 All rights reserved.
25
4
4
Содержание VLT AAF006
Страница 2: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Active Filter AAF006 www danfoss com drives...
Страница 3: ......
Страница 91: ...W Wire access 11 Index Operating Instructions 88 Danfoss A S 09 2014 All rights reserved MG90V302...
Страница 92: ...Index Operating Instructions MG90V302 Danfoss A S 09 2014 All rights reserved 89...