4.
Remove the screwdriver. The cable is now
mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screwdriver (maximum 0.4x2.5 mm) in the
square hole.
2.
Pull out the cable.
4.2.15 Unscreened Control Wires
CAUTION
INDUCED VOLTAGE
Run input power and control wiring in separate metallic
conduits or raceways for high-frequency noise isolation.
Failure to isolate power and control wiring could result
in less than optimum controls and associated equipment
performance.
Isolate control wiring, including CT wires, from the high-
voltage power wiring. When screened/armoured cable is
not used, ensure that control wires are twisted pairs and
keep the maximum possible distance between mains wire
and control cables.
Long control cables and analog signals may result in 50/60
Hz ground loops due to noise from mains supply cables.
If ground loops occur, break the screen or insert a 100 nF
capacitor between screen and chassis, if needed.
12
13
18
19
27
29
32
33
20
37
+24
VDC
0
VDC
130B
T106.10
PNP (Source)
Digital input wiring
Illustration 4.20 Input Polarity of Control Terminals, PNP
NPN (Sink)
Digital input wiring
12
13
18
19
27
29
32
33
20
37
+24
VDC
0
VDC
130B
T107.11
Illustration 4.21 Input Polarity of Control Terminals, NPN
NOTICE
To comply with EMC emission specifications, use
screened/armoured cables. If using unscreened control
cables, use ferrite cores to improve EMC performance.
Connect the shields in a proper way to ensure optimum
electrical immunity.
130B
T340.10
Illustration 4.22 Connecting Shielded Control Cables
Electrical Installation
Operating Instructions
MG90V302
Danfoss A/S © 09/2014 All rights reserved.
27
4
4
Содержание VLT AAF006
Страница 2: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Active Filter AAF006 www danfoss com drives...
Страница 3: ......
Страница 91: ...W Wire access 11 Index Operating Instructions 88 Danfoss A S 09 2014 All rights reserved MG90V302...
Страница 92: ...Index Operating Instructions MG90V302 Danfoss A S 09 2014 All rights reserved 89...