CT terminals specification
CT number
3 (one for each phase)
The AAF burden equals
2 m
Ω
Secondary current rating
1 A or 5 A (hardware set-up)
Accuracy
Class 0.5 or better
Digital inputs
Programmable digital inputs
2 (4)
Terminal number
18, 19, 27
1)
, 29
1)
Logic
PNP or NPN
Voltage level
0-24–V DC
Voltage level, logic 0 PNP
<5 V DC
Voltage level, logic1 PNP
>10 V DC
Voltage level, logic 0 NPN
>19 V DC
Voltage level, logic 1 NPN
<14 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Control card, RS485 serial communication
Terminal number
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0–24 V
Maximum output current (sink or source)
40 mA
1) Terminal 27 and 29 can also be programmed as input.
Control card, 24 V DC output
Terminal number
13
Maximum load
200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Surroundings
Enclosure
IP21, IP54
Vibration test
1.0 g
Relative humidity
5% - 95% (IEC 721-3-3; class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class kD
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature
- with derating
maximum 50
°
C
- at full continuous output current
max. 40
°
C
Minimum ambient temperature
-10
°
C
Temperature during storage/transport
-25 to +65
°
C
Maximum altitude above sea level without derating
1000 m
Maximum altitude above sea level with derating
3000 m
EMC standards, Emission
EN 61800-3-4
EMC standards, Immunity
EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Specifications
Operating Instructions
82
Danfoss A/S © 09/2014 All rights reserved.
MG90V302
9
9
Содержание VLT AAF006
Страница 2: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT Active Filter AAF006 www danfoss com drives...
Страница 3: ......
Страница 91: ...W Wire access 11 Index Operating Instructions 88 Danfoss A S 09 2014 All rights reserved MG90V302...
Страница 92: ...Index Operating Instructions MG90V302 Danfoss A S 09 2014 All rights reserved 89...