VLT
®
8000 AQUA
the relay is active, a "0" indicates inactive. Paramater
007 uses an 8-bit word with the last two positions
not used. Relays 6-9 are provided with the cascade
controller and four relay option cards
Pulse reference [Hz]
states a pulse frequency in
Hz connected to terminal 17 or terminal 29.
External reference [%]
gives the sum of the external
references as a percentage (the sum of analog/
pulse/serial communication) in the range from
Minimum
reference
, Ref
MIN
to
Maximum reference
, Ref
MAX
.
Heat sink temp. [°C]
states the present heat sink
temperature of the frequency converter. The cut-out
limit is 90 ± 5°C; cutting back in occurs at 60 ± 5°C.
Communication option card warning [Hex]
gives a
warning word if there is a fault on the communication
bus. This is only active if communication options
have been installed. Without communication
options, 0 Hex is displayed.
LCP display text
shows the text programmed in
parameter 533
Display text 1
and 534
Display text
2
via LCP or the serial communication port.
LCP procedure for entering text
After selecting
Display Text
in parameter 007, select
display line parameter (533 or 534) and press the
CHANGE DATA
key. Enter text directly into the
selected line by using
UP, DN & LEFT, RIGHT
arrow
keys on the LCP. The UP and DN arrow keys scroll
through the available characters. The Left and Right
arrow keys move the cursor through the line of text.
To lock in the text, press the
OK
key when the line of text
is completed. The
CANCEL
key will cancel the text.
The available characters are:
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Æ Ø Å Ä Ö Ü É Ì Ù è . / - ( ) 0 1 2 3 4 5 6 7 8 9
’
space
’
’
space
’
is the default value of parameter 533 &
534. To erase a character that has been entered,
it must be replaced with
’
space
’
.
Status word
displays the actual drive status
word (see parameter 608).
Control word
displays the actual control word
(see parameter 607).
Alarm word
displays the actual alarm word.
PID output
shows the calculated PID output
in the display in either Hz [33] or percentage
of max frequency [34].
008 Small display readout 1.1
(SMALL READOUT 1)
Value:
See parameter 007
Large display readout
✭
Reference [Unit]
[2]
Function:
This parameter enables a choice of the first of three data
values to be shown on the display, line 1, position 1.
This is a useful function, i.a. when setting the
PID regulator, in order to see how the process
reacts to a change of reference.
For display read-outs, press the [DISPLAY MODE]
button. Data option
LCP display text
[29] cannot
be selected with
Small display readout
.
Description of choice:
There is a choice of 33 different data values, see
parameter 007
Large display readout
.
009 Small display readout 1.2
(SMALL READOUT 2)
Value:
See parameter 007
Large display readout
✭
Motorcurrent [A]
[5]
Function:
See the functional description for parameter 008
Small
display readout
. Data option
LCP display text
[29]
cannot be selected with
Small display readout
.
Description of choice:
There is a choice of 33 different data values, see
parameter 007
Large display readout.
010 Small display readout 1.3
(SMALL READOUT 3)
Value:
Se parameter 007
Large display readout
✭
Power [kW]
[6]
Function:
See the functional description for parameter 008
Small data readout.
Data option
LCP display text
[29]
cannot be selected with
Small display readout
.
Description of choice:
There is a choice of 33 different data values, see
parameter 007
Large display readout.
011 Unit of local reference
(UNIT OF LOC REF)
Value:
Hz (HZ)
[0]
✭
% of output frequency range (%) (% OF FMAX)
[1]
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
96
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...