VLT
®
8000 AQUA
■
Technical data, mains supply 3 x 200 - 240 V
According to international requirements
VLT type
8006
8008
8011
Output current
4)
I
VLT,N
[A]
16.7
24.2
30.8
I
VLT, MAX
(60 s) [A]
18.4
26.6
33.9
Output power (240 V)
S
VLT,N
[kVA]
6.9
10.1
12.8
Typical shaft output
P
VLT,N
[kW]
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
5
7.5
10
Max. cable cross-section to
motor
and DC-bus
[mm
2
]/[AWG]
10/8
16/6
16/6
Max. input current
(200 V) (RMS)I
L,N
[A]
16.0
23.0
30.0
Max. cable
cross-section power
[mm
2
]/[AWG]
2 )
4/10
16/6
16/6
Max. pre-fuses
[-]/UL
1)
[A]
35/30
50
60
Efficiency
3)
0.95
0.95
0.95
Weight IP 20
[kg/lbs]
23/51
23/51
23/51
Weight IP 54
[kg/lbs]
35/77
35/77
38/84
Power loss at
max. load. [W]
Total
194
426
545
Enclosure
VLT type
IP 20/ NEMA 1, IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
MG.83.A2.02 - VLT is a registered Danfoss trademark
36
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...