VLT
®
8000 AQUA
■
Factory settings
PNU
#
Parameter
description
Factory setting
Range
Changes
during
operation
4-setup
Con-
version
index
Data
type
001
Language
English
Yes
No
0
5
002
Active Setup
Setup 1
Yes
No
0
5
003
Copying of Setup
No copying
No
No
0
5
004
LCP copy
No copying
No
No
0
5
005
Max value of user-defined readout
100.00
0 - 999.999,99
Yes
Yes
-2
4
006
Unit for user-defined readout
No unit
Yes
Yes
0
5
007
Big display readout
Frequency, % of max.
Yes
Yes
0
5
008
Small display readout 1.1
Reference, Unit
Yes
Yes
0
5
009
Small display readout 1.2
Motor current, A
Yes
Yes
0
5
010
Small display readout 1.3
Power, HP
Yes
Yes
0
5
011
Unit of local reference
Hz
Yes
Yes
0
5
012
Hand start on LCP
Enable
Yes
Yes
0
5
013
OFF/STOP on LCP
Enable
Yes
Yes
0
5
014
Auto start on LCP
Enable
Yes
Yes
0
5
015
Reset on LCP
Enable
Yes
Yes
0
5
016
Lock for data change
Not locked
Yes
Yes
0
5
017
Operating state at power-up,
local control
Auto restart
Yes
Yes
0
5
100
Configuration
Open loop
No
Yes
0
5
101
Torque characteristics
Automatic Energy
Optimisation
No
Yes
0
5
102
Motor power P
M,N
Depends on the unit
1.1-400 kW
(1.5-600 HP
No
Yes
1
6
103
Motor voltage, U
M,N
Depends on the unit
208/480/575 V
No
Yes
0
6
104
Motor frequence, f
M,N
60 Hz/
50 Hz
24-120 Hz
No
Yes
0
6
105
Motor current, I
M,N
Depends on the unit
0.01 - I
VLT,MAX
No
Yes
-2
7
106
Rated motor speed, n
M,N
Depends on
par. 102 Motor power
100-60000 rpm
No
Yes
0
6
107
Automatic motor adaptation,AMA
Optimisation disable
No
No
0
5
108
VT start voltage
Depends on par. 103
0.0 - par. 103
Yes
Yes
-1
6
109
Resonance dampening
100 %
0 - 500 %
Yes
Yes
0
6
110
High brake-away torque
0.0 sec.
0.0 - 0.5 sec.
Yes
Yes
-1
5
111
Start delay
0.0 sec.
0.0 - 120.0 sec.
Yes
Yes
-1
6
112
Motor preheater
Disable
Yes
Yes
0
5
113
Motor preheater DC current
50 %
0 - 100 %
Yes
Yes
0
6
114
DC braking current
50 %
0 - 100 %
Yes
Yes
0
6
115
DC braking time
10 sec.
0.0 - 60.0 sec.
Yes
Yes
-1
6
116
DC brake cut-in frequency
OFF
0.0-par. 202
Yes
Yes
-1
6
118
Motor power factor
0.75
0.50-0.99
No
Yes
0
6
117
Motor thermal protection
ETR trip 1
Yes
Yes
0
5
119
Load compensation at low speed
100 %
0 - 300 %
Yes
Yes
0
6
120
Load compensation at high speed
100 %
0 - 300 %
Yes
Yes
0
6
121
Slip compensation
100 %
-500 - 500 %
Yes
Yes
0
3
122
Slip compensation time constant
0.50 sec.
0.05 - 5.00 sec.
Yes
Yes
- 2
6
123
Stator resistance
Depends on the choice
of motor
No
Yes
- 4
7
124
Stator reactance
Depends on the choice
of motor
No
Yes
- 2
7
) Global factory setting different from North American factory setting.
MG.83.A2.02 - VLT is a registered Danfoss trademark
196
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...