VLT
®
8000 AQUA
Programming
External Ref
MIN
- Ref
MAX
⇒
0-20 mA
and
External Ref
MIN
- Ref
MAX
⇒
4-20 mA
and
External Ref
MIN
- Ref
MAX
⇒
0-32000 p
which
generates an output signal proportional to the resulting
reference value in the interval
Minimum reference, Ref
MIN
- Maximum reference, Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
⇒
0-20 mA
and
FB
MIN
-FB
MAX
⇒
4-20mA
and
FB
MIN
-FB
MAX
⇒
0-32000 p
an output signal
proportional to the reference value in the interval
Minimum feedback, FB
MIN
- Maximum feedback,
FB
MAX
(parameters 413/414) is obtained.
0 - I
VLT,MAX
⇒
0-20 mA
and
0 - I
VLT,MAX
⇒
4-20 mA
and
0 - I
VLT,MAX
⇒
0-32000 p
, an output signal
proportional to the output current in the interval
0 - I
VLT,MAX
is obtained.
0 - p
NOM
⇒
0-20 mA
and
0 - p
NOM
⇒
4-20 mA
and
0 - p
NOM
⇒
0-32000 p
, which generates an
output signal proportional to the present output
power. 20 mA corresponds to the value set in
parameter 102
Motor power, P
M,N
.
0.0 - 100.0%
⇒
0 - 20 mA
and
0.0 - 100.0%
⇒
4 - 20 mA
and
0.0 - 100.0%
⇒
0 - 32.000
pulses which generates an
output signal proportional to the value (0.0-100.0%)
received by serial communication. Writing from Serial
communication is done to parameter 364 (terminal
42) and 365 (terminal 45). This function is limited to
the following protocols: FC bus, Profibus, LonWorks
FTP, DeviceNet, and Modbus RTU.
Motor alternation
A relay or digital output can be used
in conjunction with output contactors to alternate the
frequency converter
’
s output between motors based
on an internal timer. See parameters 433 and 434 for
further information and programming information.
320 Terminal 42, output, pulse scaling
(AO 42 PULS SCALE)
Value:
1 - 32000 Hz
✭
5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value.
321 Terminal 45, output
(AO 45 FUNCTION)
Value:
See description of parameter 319
Terminal 42, Output.
Function:
This output can function both as a digital or an analog
output. When used as a digital output (data value
[0]-[26]) it generates a 24 V (max. 40 mA) signal. For
the analog outputs (data value [27] - [41]) there is a
choice of 0-20 mA, 4-20 mA or a pulse sequence.
Description of choice:
See description of parameter 319
Terminal 42, Output.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
127
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...