VLT
®
8000 AQUA
Installation
■
Technical data, mains supply 3 x 380 - 480 V
According to international requirements
VLT type
8152
8202
8252
8302
8352
Output
current
I
VLT,N
[A] (380-440 V)
212
260
315
395
480
I
VLT, MAX
(60 s) [A] (380-440 V)
233
286
347
435
528
I
VLT,N
[A] (441-480 V)
190
240
302
361
443
I
VLT, MAX
(60 s) [A] (441-480 V)
209
264
332
397
487
Output
power
S
VLT,N
[kVA] (400 V)
147
180
218
274
333
S
VLT,N
[kVA] (460 V)
151
191
241
288
353
Typical shaft output (380-440 V) P
VLT,N
[kW]
110
132
160
200
250
Typical shaft output (441-480 V) P
VLT,N
[HP]
150
200
250
300
350
Max. cable cross-section to motor and
DC-bus [mm
2
]
2) 4) 5)
2x70
2x70
2x185
2x185
2x185
Max. cable cross-section to motor and
DC-bus [AWG]
2) 4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Min. cable cross-section to motor and
DC-bus [mm
2
/AWG]
2) 4) 5)
35/2
35/2
35/2
35/2
35/2
Max. input
current
I
L,N
[A] (380 V)
208
256
317
385
467
(RMS)
I
L,N
[A] (480 V)
185
236
304
356
431
Max. cable cross-section to power [mm
2
]
2)
4) 5)
2x70
2x70
2x185
2x185
2x185
Max. cable cross-section to power [AWG]
2)
4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Max. pre-
fuses
[-]/UL
1)
[A]
300/300
350/350
450/400
500/500
630/600
Weight
IP 00/
Chassis
[kg/lbs]
82/181
91/201
112/247
123/271
138/304
Weight
IP 20/
NEMA 1
[kg/lbs]
96/212
104/229
125/276
136/300
151/333
Weight
IP 54/
NEMA 12
[kg/lbs]
96/212
104/229
125/276
136/300
151/333
Efficiency at rated frequency
0.98
Power loss
at max.
load.
[W]
2619
3309
4163
4977
6107
Enclosure
IP 00/Chassis/IP 21/NEMA 1/IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable
cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.83.A2.02 - VLT is a registered Danfoss trademark
41
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...