VLT
®
8000 AQUA
All about VLT 8000
AQUA
■
Factory settings
PNU
#
Parameter
description
Factory setting
Range
Changes
during
operation
4-setup
Conver-
sion
index
Data
type
300
Terminal 16 Digital input
Reset
Yes
Yes
0
5
301
Terminal 17 Digital input
No operation
Yes
Yes
0
5
302
Terminal 18 Digital input
Start
Yes
Yes
0
5
303
Terminal 19 Digital input
Reversing
Yes
Yes
0
5
304
Terminal 27 Digital input
Safety interlock/
Coasting stop,
inverse
Yes
Yes
0
5
305
Terminal 29 Digital input
Jog
Yes
Yes
0
5
306
Terminal 32 Digital input
No operation
Yes
Yes
0
5
307
Terminal 33 Digital input
No operation
Yes
Yes
0
5
308
Terminal 53, analog input voltage
No operation
Yes
Yes
0
5
309
Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
310
Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
311
Terminal 54, analog input voltage
No operation
Yes
Yes
0
5
312
Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
313
Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
314
Terminal 60, analog input voltage
Reference
Yes
Yes
0
5
315
Terminal 60, min. scaling
4.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
316
Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
317
Time out
10 sec.
1 - 99 sec.
Yes
Yes
0
5
318
Function after time out
Off
Yes
Yes
0
5
319
Terminal 42, output
0 - I
MAX
⇒
4-20 mA
Yes
Yes
0
5
320
Terminal 42, output
pulse scaling
Yes
Yes
0
6
321
Terminal 42, output
0 - f
MAX
⇒
0-20 mA
Yes
Yes
0
5
322
Terminal 45, output,
Yes
Yes
pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
323
Relay 1, output function
No alarm
Yes
Yes
0
5
324
Relay 01, ON delay
0.00 sec.
0 - 600 sec.
Yes
Yes
0
6
325
Relay 01, OFF delay
2.00 sec.
0 - 600 sec.
Yes
Yes
0
6
326
Relay 2, output function
Running
Yes
Yes
0
5
327
Pulse reference,
max frequency
5000 Hz
Depends on
input terminal
Yes
Yes
0
6
328
Pulse feedback, max. frequency
25000 Hz
0 - 65000 Hz
Yes
Yes
0
6
364
Terminal 42, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
365
Terminal 45, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
) Coasting stop, inverse is global factory setting different from North American factory setting.
Changes during operation:
"Yes" means that the parameter can be changed,
while the frequency converter is in operation. "No"
means that the frequency converter must be stopped
before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same para-meter can have four different data
values. "No" means that the data value will be
the same in all four setups.
Conversion index:
This number refers to a conversion figure to be
used when writing or reading to or from a frequency
converter by means of serial communication.
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type:
Data type shows the type and length of the
telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
MG.83.A2.02 - VLT is a registered Danfoss trademark
199
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...