VLT
®
8000 AQUA
Programming
Connection examples
Setup change
-
Selection of Setup using terminals 32 and 33.
Parameter 306 =
Selection of Setup
, lsb [4]
Parameter 307 =
Selection of Setup
, msb [4]
Parameter 002 =
MultiSetup
[5].
003 Copying of Setups
(SETUP COPY)
Value:
✭
No copying (NO COPY)
[0]
Copy active Setup to Setup 1
(COPY TO SETUP 1)
[1]
Copy active Setup to Setup 2
(COPY TO SETUP 2)
[2]
Copy active Setup to Setup 3
(COPY TO SETUP 3)
[3]
Copy active Setup to Setup 4 (COPY TO SETUP 4) [4]
Copy active Setup to all
(COPY TO ALL)
[5]
Function:
A copy is made from the active Setup selected in
parameter 002
Active Setup
to the Setup or Setups
selected in parameter 003
Copying of Setups
.
NB!:
Copying is only possible in Stop mode (motor
stopped on a Stop command).
Description of choice:
The copying starts when the required copying function
has been selected and the [OK] key has been pressed.
The display indicates when copying is in progress.
004 LCP copy
(LCP COPY)
Value:
✭
No copying (NO COPY)
[0]
Upload all parameters
(UPLOAD ALL PARAMET.)
[1]
Download all parameters
(DOWNLOAD ALL PARAM.)
[2]
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
[3]
Function:
Parameter 004
LCP copy
is used if the integrated
copying function of the control panel is to be used.
This function is used if all parameter Setups are
to be copied from one frequency converter to
another by moving the control panel.
Description of choice:
Select
Upload all parameters
[1] if all parameter values
are to be transmitted to the control panel.
Select
Download all parameters
[2] if all transmitted
parameter values are to be copied to the frequency
converter on which the control panel has been mounted.
Select
Download power-independent par
. [3] if only the
power-independent parameters are to be downloaded.
This is used if downloading to a frequency converter
that has a different rated power than the one from
where the parameter Setup originates.
NB!:
Uploading/Downloading can only be carried
out in the Stop mode.
■
Setup of user-defined readout
Parameter 005
Max. value of user-defined readout
and 006
Unit for user-defined readout
allow users
to design their own readout which can be seen
if user-defined readout has been selected under
display readout. The range is set in parameter 005
Max. value of user-defined readou
t and the unit is
determined in parameter 006
Unit for user-defined
readout
. The choice of unit decides whether the
ratio between the output frequency and the readout
is a linear, square or cubed ratio.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
93
Содержание VLT 8000 AQUA series
Страница 29: ...VLT 8000 AQUA Introduction TYPE CODE Table Ordering form MG 83 A2 02 VLT is a registered Danfoss trademark 29 ...
Страница 52: ...VLT 8000 AQUA Mechanical dimensions MG 83 A2 02 VLT is a registered Danfoss trademark 52 ...
Страница 60: ...VLT 8000 AQUA All enclosure types VLT 8152 8652 380 480 V MG 83 A2 02 VLT is a registered Danfoss trademark 60 ...
Страница 63: ...VLT 8000 AQUA Installation MG 83 A2 02 VLT is a registered Danfoss trademark 63 ...