VLT® 5000 Crane
326 RELAY 4-5 FUNCT.
Value:
See parameter 341
Function:
This output activates a relay switch.
Relay switch 04 can be used for bringing status and
warnings. The relay is activated when the conditions
for the relevant data values have been fulfilled.
Description of choice:
See description of parameter 341.
Connections - see the below drawing.
329 ENCODER PULSES
Value:
✭
1024 pulses /rev. (1024)
[1024]
Function:
This is where to set the encoder pulses per revolution.
This parameter is only available in
Speed control,
closed loop
(parameter 100).
Description of choice:
Read the correct value from the encoder.
Signal level 0 - 5V (RS 422)
Signals necessary: A, Inv. A, B, Inv. B, Z and Inv. Z.
341 SIGNAL OUTPUT 46
Value:
✭
No operation (NO OPERATION)
[0]
Control ready (CONTROL READY)
[1]
Unit ready (UNIT READY)
[2]
Enabled (ENABLED)
[3]
VLT running (VLT RUNNING)
[4]
VLT running and no warning
(RUNNING/NO WARNING)
[5]
VLT running on reference and no warning
(RUN ON REF/NO WARN)
[6]
Positioning (POSITIONING)
[7]
Normal run (NORMAL RUN)
[8]
Alarm (ALARM)
[9]
Alarm or warning (ALARM OR WARNING)
[10]
Torque limit motor mode
(TORQUE LIMIT MOTOR M)
[11]
Braking, no brake warning
(BRAKING, NO BR. WARN.)
[12]
Brake fault (IGBT SHORT-CIRCUIT FAULT)
[13]
Mechanical brake control
(MECH. BRAKE CONTROL)
[14]
Mechanical brake ready no fault
(MECH. BRAKE RDY/NO F)
[15]
Thermal warning (THERMAL WARNING)
[16]
Unit ready and no thermal warning
(READY/NO THERM WARN)
[17]
Unit ready and no over/undervoltage
(RDY NO OVER/UNDERVOL)
[18]
Control word bit 11 (CTRL WORD BIT 11)
[19]
Control word bit 12 (CTRL WORD BIT 12)
[20]
Function:
Selects the function for output on the digital terminal
46. If the condition of the selected function is true, the
output level is 24 V (active), otherwise it is 0 V (inactive).
Description of choice:
No operation
Selected if the output should not react to any
signals. The output is 0 V.
Control ready
The frequency converter is ready for use; the
control card receives supply voltage.
Unit ready
The frequency converter control card is receiving
a supply signal and the frequency converter
is ready for operation.
Enabled
The frequency converter is ready for use; no start or stop
command has been given (start/disable). No warning.
Running
This signal is active when a start command has
been given or a stop command has been given
and the drive has not stopped.
Running and no warning
This signal is active when a start command has been
given or a stop command has been given and the
drive has not stopped. No warning.
Running on reference and no warning
Speed according to reference. No warning.
Positioning
The output is active during positioning.
Normal run
The output is active during normal run, ie.
not during positioning.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.N4.02 - VLT is a registered Danfoss trademark