VLT® 5000 Crane
316
AI 60 SCALE HIGH
Value:
0.0 - 20.0 mA
✭
20.0 mA
Function:
This parameter is used for setting the signal value that
is to correspond to the maximum reference value,
parameter 205
Maximum reference value, Ref
MAX
.
317 LIVE ZERO TIME O
Value:
1 - 99 sec.
✭
10 sec.
Function:
If the signal value of the reference signal connected
to one of the input terminals 53 or 60 falls below 50
% of the minimum scaling for a period longer than
the time set, the function selected in parameter 318
Function after time out
will be activated. This function
is only active if in parameter 309
Terminal 53, min.
scaling
a value higher than 1 Volt has been selected,
or if in parameter 315/353
Terminal 58, min. scaling
a value higher than 2 mA has been selected.
Description of choice:
Set the required time.
318 LIVE ZERO FUNCT.
Value:
✭
No operation (NO OPERATION)
[0]
Freeze output frequency (FREEZE OUTPUT FREQ.) [1]
Stop (STOP)
[2]
Jog (JOG)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter allows a choice of the function
to be activated after the expiration of the Time
out (parameter 317
Time out
).
Description of choice:
The output frequency of the drive can be:
-
frozen at the present frequency [1]
-
overruled to stop [2]
-
overruled to jog frequency [3]
-
overruled to max. output frequency [4]
-
overruled to stop with subsequent trip [5]
319
AO 42 FUNCTION
Value:
✭
No operation (NO OPERATION)
[40]
0 - 100 Hz = 0-20mA
(0 - 100 HZ = 0-20MA)
[41]
0 - 100 Hz = 4-20 mA
(0 - 100 HZ = 4-20 MA)
[42]
Ref min-max = 0-20 mA
(REF MIN-MAX = 0-20 MA)
[43]
Ref min.-max. 4-20 mA
(REF MIN-MAX = 4-20 MA)
[44]
FB min-max 0-20 mA
(FB MIN-MAX = 0-20 MA)
[45]
FB min-max 4-20 mA
(FB MIN-MAX = 4-20 MA)
[46]
0 - I
max
= 0-20 mA
(0- I
MAX
= 0-20 MA)
[47]
0-I
max
4-20 mA
(0-I
MAX
= 4-20 MA)
[48]
0-T
lim
0-20 mA
(0-T
LIM
= 0-20 MA)
[49]
0-T
lim
4-20 mA
(0-T
LIM
= 4-20 MA)
[50]
0 - T
nom
= 0-20 mA
(0 - T
NOM
= 0-20 MA)
[51]
0 - T
nom
= 4-20 mA
(0 - T
NOM
= 4-20 MA)
[52]
0 - P
nom
= 0-20mA
(0 - P
NOM
= 0-20MA)
[53]
0 - P
nom
= 4-20mA
(0 - P
NOM
= 4-20MA)
[54]
0 - Speedmax = 0-20mA
(0 - SPEEDMAX = 0-20MA)
[55]
0 - Speedmax = 4-20mA
(0 - SPEEDMAX = 4-20MA)
[56]
± 160% torque = 0-20mA
(± 160% TORQUE = 0-20MA)
[57]
± 160% torque = 4-20mA
(± 160% TORQUE = 4-20MA)
[58]
Function:
The analogue output can be used for stating a
process value. It is possible to choose two types of
output signals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down
resistor of 500
must be fitted to common
(terminal 39). If the output is used as a current
output the resulting resistance from the equipment
connected may not exceed 500
.
Description of choice:
No operation
. Is selected if the analogue
output is not to be used.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port