VLT® 5000 Crane
PNU
Parameter
Range
Factory setting
Changes
Unit
Conversion
Data
Protection
#
7xx
description
Crane functions
during
operation
index
index
type
level
701
Load low
0 - 5000RPM
2500RPM
No
11
67
6
1
702
Load high
0 - 1250RPM
1250RPM
No
11
67
6
1
703
Load monitoring
Enable
No
0
0
5
1
704
Low speed at error
5 - 200RPM
50 RPM
No
11
67
5
1
705
Brake on RPM
0 - 50RPM
20 RPM
No
11
67
5
1
707
Hoist direction
Forward
No
0
0
5
1
708
Start torque
0 - 170%
100%
No
27
0
5
1
709
Ramp torque
0.2 - 2 sec.
0.2 sec.
No
4
-1
5
1
712
Brake monitoring
Enable
Yes
0
0
5
1
713
Derating lowering
0.6 - 1
0.8
No
0
-2
5
1
714
Derating hoisting
0.6 - 1
1
No
0
-2
5
1
715
Mech. brake on
delay
0,1 - 20 sec.
0,5 sec.
Yes
4
-1
5
1
716
Mech. brake off
delay
0,1 - 20 sec.
0,5 sec.
Yes
4
-1
5
1
718
Encoder
monitoring
Enable
No
0
0
5
1
720
Drum inertia 1
0 - 1
Depends on unit
No
0
-4
6
1
721
Gear ratio 1
0 - 200
Depends on unit
No
0
-2
6
1
722
Gear inertia 1
0 - 1
Depends on unit
No
0
-4
6
1
723
Mean radius 1
0 - 2
Depends on unit
No
0
-3
6
1
724
Drum inertia 2
0 - 1
Depends on unit
No
0
-4
6
1
725
Gear ratio 2
0 - 200
Depends on unit
No
0
-2
6
1
726
Gear inertia 2
0 - 1
Depends on unit
No
0
-4
6
1
727
Mean radius 2
0 - 2
Depends on unit
No
0
-3
6
1
740
Power limit function
Constant power
No
0
0
5
1
741
Mechanical speed
N1
Depends on unit
No
11
0
6
1
742
Power at N1
Depends on unit
No
9
1
6
1
743
Mechanical speed
at N2
Depends on unit
No
11
67
6
1
744
Power at N2
Depends on unit
No
9
1
6
1
745
Mechanical speed at
N3
Depends on unit
No
11
67
6
1
746
Power at N3
Depends on unit
No
9
1
6
1
747
Mechanical speed at
N4
Depends on unit
No
11
67
6
1
748
Power at N4
Depends on unit
No
9
1
6
1
749
Mechanical speed
N5
Depends on unit
No
11
67
6
1
750
Power at N5
Depends on unit
No
9
1
6
1
751
Mechanical speed
N6
Depends on unit
No
11
67
6
1
752
Power at N6
Depends on unit
No
9
1
6
1
753
Mechanical speed
N7
Depends on unit
No
11
67
6
1
754
Power at N7
Depends on unit
No
9
1
6
1
755
Power Loss N1
Depends on unit
No
9
1
6
1
756
Power Loss N2
Depends on unit
No
9
1
6
1
757
Power Loss N3
Depends on unit
No
9
1
6
1
758
Power Loss N4
Depends on unit
No
9
1
6
1
759
Power Loss N5
Depends on unit
No
9
1
6
1
760
Power Loss N6
Depends on unit
No
9
1
6
1
761
Power Loss N7
Depends on unit
No
9
1
6
1
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.N4.02 - VLT is a registered Danfoss trademark