VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA PROFIBUS
Function:
This parameter contains the profile number which a
Profibus slave supports. This parameter is read only
and only accessible via the Profibus V1 communication.
967 Control word
(CONTROL WORD)
Value:
16 bit binary code
No control panel access
Function:
This parameter is read only and can only be accessed
via the Profibus communication.
968 Status word
(STATUS WORD)
Value:
Read only (16 bit binary code)
No control panel access
Function:
This parameter is read only and only accessible
via the Profibus communication.
970 Edit setup selection
(EDIT SETUP SELECT)
Value:
Factory Setup
[0]
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Setup 3 (SETUP 3)
[3]
Setup 4 (SETUP 4)
[4]
✭
Active setup (ACTIVE SETUP)
[ 5]
Function:
This parameter is to be used for accessing
frequency converter parameters in various setups
from a master class 1 (e.g. PLC).
Please see section
Read/Write on VLT frequency
converter parameters
.
971 Store data values
(STORE DATA VALUE)
Value:
✭
No action (OFF)
[0]
Store active setup (STORE ACTIVE SETUP)
[1]
Store edit setup (STORE EDIT SETUP)
[ 2]
Store all setups (STORE ALL SETUPS)
[ 3]
Function:
Parameter values modified through PROFIBUS master
class 1 are only saved in RAM, i.e. the modifications
are lost in the event of a power failure. This parameter
is used to activate a function by means of which all
parameter values are saved in EEPROM, preserving
them even in the case of a power failure.
Description of choice:
-
No action:
The function is not active.
-
Store active setup:
All parameter setups of the active
setup are saved in EEPROM. The value returns to Not
active after all parameter values have been saved.
-
Store edit setup (par. 970):
All parameter
setups of the setup being processed are saved in
EEPROM. The value returns to Not active after all
parameter values have been saved.
-
Store all setups:
All parameter setups in all setups
are saved in EEPROM. The value returns to Not active
after all parameter values have been saved.
980-982 Defined parameters
(DEFINED PARAM.)
Value:
Read only
Function:
The three parameters hold a list of all the parameters
that are defined in the VLT 5000/5000 FLUX/6000
HVAC and 8000 AQUA. It is possible to read single
elements of the list by DP by using the corresponding
subindex. The subindexes start at 1 and follow
the order of the parameter numbers.
Each parameter holds up to 116 elements
(parameter numbers).
When a 0 is returned as parameter number the list ends.
990-992 Modified parameters
(MODIFI. PARAM.)
Value:
Read only
Function:
The three parameters hold a list of all the VLT 5000/5000
FLUX/6000 HVAC and 8000 AQUA parameters that
have been changed from factory setting. It is possible
to read single elements of the list by DP by using
the corresponding subindex. The subindexes start
at 1 and follow the order of the parameter numbers.
Each parameter holds up to 116 elements (parameter
MG.90.G1.02 - VLT is a registered Danfoss trademark
40