VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA PROFIBUS
■
Status word according to fc standard
The Status word is used to notify a master (e.g.
a PC) about the status of a slave.
Bit
Bit = 0
Bit =1
00
Control not ready
Ready
01
VLT not ready
Ready
02
Coasting
Enable
03
No error
Trip
04
Not in use
05
Not in use
06
Not in use
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local operation
Bus control
10
Not in operation
range
Frequency limit OK
11
No operation
Operation
12
VLT OK
Stopped, autostart
13
Voltage OK
Limit exceeded
14
Torque OK
Limit exceeded
15
Timer OK
Limit exceeded
Bit 00, Control not ready/ready:
Bit 00 = "0" means that the frequency converter
has switched off due to malfunction.
Bit 00 = "1" means that the frequency converter
control is ready, but that there is not necessarily
a supply to the power unit present (in the case of
external 24 V supply of the control card).
Bit 02, Coasting/Enable
Bit 02 = "0" means that the bit 03 of the Control
word is "0" (Coasting) or that the frequency
converter has tripped.
Bit 02 = "1" means that the bit 03 of the Control word
is "1" and that the frequency converter has not tripped.
NB!:
The description of the other bits can be found in
the section "Status word according to Profidrive".