![Danfoss VLT 5000 Series Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/danfoss/vlt-5000-series/vlt-5000-series_operating-instructions-manual_3439550040.webp)
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA PROFIBUS
Parameters
NB!:
When parameters 927 and 928 are deactivated,
the "Warning 34" in the display of the frequency
converter will also be suppressed.
Description of choice:
If Disable [0] is selected, process control through
Profibus is not active, but standard RS 485 is active. If
Enable [1] is selected, process control through Profibus
is active, but standard RS 485 is not active.
NB!:
Please note, that the motor may start without
advance warning when parameter 928 has been
changed, and start commands are present.
953 Warning parameter 1
(WARN. PARA)
Value:
Read only
Function:
In this parameter it is possible to read out warning
messages via standard bus or Profibus. This
parameter is not available via LCP, but the warning
message can be seen by choosing Com warning
word as display readout. A bit is assigned to
every warning (see the following list).
Bit
Bit= "1" when:
0 LSB
Connection with DP-master is not ok
1
Not used
2
FDL (Field-bus Data link Layer) is not ok
3
Clear dat command received
4
Actual value is not updated
5
Spontaneous message FIFO overflow
6
PROFIBUS ASIC is not transmitting
7
Initialising of PROFIBUS option is not ok
8
Not used
9
Not used
10
Not used
11
Not used
12
Fatal DPR-handling error/Error code
during init.: Bit 0
13
Fatal DPR-handling error/Error code
during init.: Bit 1
14
Fatal DPR-handling error/Error code
during init.: Bit 2
15 MSB
Fatal DPR-handling error/Error code
during init.: Bit 3
Explanation of errror codes:
Depending of Bit 7 the corresponding error codes
can be seen from Bit 12-15.
Bit 7 = 1: Initialisation failure
Code
0
OK
1
Init. channel not empty
2
No resp. on command "Init. SPC3 controller"
3
No resp. on command "No action"
4
No resp. on writin ini.-data
5
No valid resp. on writing init.-data
6
No positive resp. on writing init.-data
Bit 7 = 0: Run time failure
Code
0
OK
1
Fatal error in warning channel
2
Fatal error in spontaneous channel
3
Fatal error in channel for input of process data
4
Fatal error in channel for out of process data
5
Fatal error in parameter channel 1
6
Fatal error in parameter channel 2
7
Fatal error in parameter channel 3
15
Fatal error in DPR form SPC3
964 Identification
Selections:
0
Manufucturer
1
Device type
2
Version
3
Firmware date year
4
Firmware date month
5
Number of axes
6
Profibus version
7
Database version
8
Power unit ID
9
BMC software
Function:
This parameter contains the identification of a Profibus
slave. This parameter is read only and only accessible
via the Profibus V1 communication.
965 Profile Number
(PROFILE NUMBER)
Value:
Profile number 1. octet Manufacturer
[3]
Profile number 2. octet
[3]
MG.90.G1.02 - VLT is a registered Danfoss trademark
39
Содержание VLT 5000 Series
Страница 63: ......