Parameter description
0.. Operation and display
Value:
0.00 - REF
MAX
004
Local reference
(Local speed)
Function:
Local reference is selected to set speed
(frequency) from the operating panel.
Note: Local reference cannot be used if
remote operation has been selected in
parameter 003.
Description of choices:
The VLT
®
frequency converter’s output
frequency can be set directly in Hz using
the +/- keys. The set value is saved 20 sec.
after the last change and remembered
after mains cut-out.
Warning:
This implies that the motor can start
without warning on mains cut-in if param-
eter 014 is changed to Auto restart [0].
- Note: In this parameter data mode is not
left automatically.
- Local reference cannot be controlled via
the serial bus, RS485.
- Data changes in parameter 004 are
blocked if parameter 010 is set at NOT
POSSIBLE.
✮
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
Value:
Disable (disable)
[0]
✭
Enable (enable)
[1]
007
Local stop
(Local stop)
Value:
Disable (disable)
[0]
✭
Enable (enable)
[1]
006
Local reset
(Local reset)
Function:
Local/reset can be selected/deselected on
the keyboard.
Function:
Local Stop can be selected/deselected.
The current status of Local Start or Local
Stop command is stored.
Description of choices:
Enable is selected if Local Stop is to be
active.
Disable is selected if one of the following
situations is required:
1) If Local Stop is activated before “Local
Stop disable” is selected, the unit can be
started with the help of the Local Start key
(if remote control has been selected, the
remote-controlled start function must be
active).
2) If Local Start is activated before “Local
Stop disable” is selected, the unit cannot
be stopped with the help of the Local Stop
key, and therefore the unit cannot be
stopped via the operating panel.
005
Display value
(Value at max)
Function:
On selection of the DISPLAY/FEED BACK
function in the display mode, a user read-
out is obtained which is a scaling of the
reference sum if “Open loop” or slip-
compensated has been selected in param-
eter 101. Unit can be selected in param-
eter 117.
Description of choices:
The programmed value will be read out
when the output frequency is equivalent to
F
MAX
(parameter 202).
Value:
1 - 9999