13
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains: 380/400/415 V
Typical shaft
Constant output
Constant output
VLT
®
type
output
current I
VLT,N
power at 415 V
[kW]
[A]
[kVA]
3002
1.1
2.8
2.0
3003
1.5
4.1
2.9
3004
2.2
5.6
4.0
3006
4.0
5.5
10.0
13.0
7.2
9.3
3008
5.5
7.5
13.0
16.0
9.3
11.5
3011
7.5
11
16.0
24.0
11.5
17.3
3016
11
15
24.0
32.0
17.3
23.0
3022
15
22
32.0
44.0
23.0
31.6
3032
22
30
44.0
61.0
31.6
43.8
3042
30
37
61.0
73.0
43.8
52.5
3052
37
45
73.0
88.0
52.3
63.3
3060
45
55
86.0
105
61.8
75.5
3075
55
75
105
139
75.5
99.9
3100
75
90
139
168
99.9
120
3125
90
110
168
205
120
147
3150
110
132
205
243
147
174
3200
132
160
243
302
174
217
3250
160
200
302
368
217
264
CT
VT
CT
VT
CT: Constant torque
VT: Variable torque (quadratic load)
CT
VT
CT
VT
CT
VT
CT: Constant torque
VT: Variable torque (quadratic load)
Sizing
Typical shaft
Constant output
Constant output
VLT
®
type
output
current I
VLT,N
power at 500 V
[kW]
[A]
[kVA]
3002
1.1
2.6
2.3
3003
1.5
3.4
2.9
3004
2.2
4.8
4.1
3006
4.0
8.2
7.1
3008
5.5
11.1
9.6
3011
7.5
11
14.5
21.7
12.6
18.8
3016
11
15
21.7
27.9
18.8
24.1
3022
15
22
27.9
41.4
24.1
36.0
3032
22
30
41.4
54.0
36.0
46.8
3042
30
37
54.0
65.0
46.8
56.3
3052
37
45
65.0
78.0
56.3
67.5
3060
55
75
77.0
96.0
66.7
83.1
3075
75
90
96.0
124
83.1
107
3100
90
110
124
156
107
135
3125
110
132
156
180
135
156
3150
132
160
180
240
156
208
3200
160
200
240
302
208
262
3250
200
250
302
361
262
313
CT
VT
Mains: 440/460/500 V
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com