114
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Index 12:
A decimal value to be converted to an
8-bit binary code.
Example:
Decimal
16
Binary
0
0
0
1
0
0
0
0
Terminal
33
32
29
27
19
18
17
16
Index 13/14:
Decimal value between 0 and 1023, where
0 corresponds to 0% and 1023 to 100% of
the selected input signal, e.g. 0-10 V.
Index 15:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a warning
according to the table below. When a
warning is given, the equivalent bit has the
value “1”.
Bit
Warning
0
Current limit
1
No motor
2
Reference fault
3
Motor overloaded
4
Inverter overloaded
5
Frequency warning low
6
Frequency warning high
7
Current warning low
8
Current warning high
9
EEPROM fault
10
24 V fault
11
Over current
12
Voltage warning high
13
Voltage warning low
14
Overvoltage
15
Undervoltage
A further description of warnings is given
on pp. 124-125.
Index 16:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a control
command according to the table on
p.
75.
When a control command is activated, the
equivalent bit has the value “1”.
Index 17:
Decimal value to be converted to a 16-bit
binary code. Each bit represents a status
report according to the table on
p.
77.
When a status report is activated, the
equivalent bit has the value “1”.
Parameter description
5.. Serial communication
502
Data read-out
(Data readout)
(Continued)