
7
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Item
Parameter
Description
Settings
Display
1
000
Language
Select: "English"
ENGLISH
2
103
Motor output
See nameplate and select closest setting
3
104
Motor voltage
See nameplate
4
105
Motor frequency
See nameplate
Items 1-4 must be carried out first.
5
106
Automatic
Select: "On".
ON
motor adaption
The compensation menus 109-113 are now tuned automatically.
During automatic motor adaption the motor should be unloaded or
loaded at max. 50%.
Automatic motor adaption is not possible in connection with
parallel running of several motors on one VLT
®
. This also applies
to motor outputs which cannot be set in parameter 103, and
synchronous, reluctance and other specialised motors.
After tuning the VLT
®
is reset by pressing the Stop/Reset key and
restarted by pressing the Start key.
Note: During automatic motor adaption the motor will start
for a short period.
6
201
Min. frequency
Set required frequency
7
202
Max. frequency
Set required frequency
8
215
Ramp-up 1
Set required ramp time
9
216
Ramp-down 1
Set required ramp time
10
Start frequency converter
This is by supplying terminals 18 and 27 with 24 V D.C. from
terminal 12 or by using an external 24 V D.C. voltage.
Quick setup
If the factory setting
has been changed
If the factory setting has been changed
initialisation must be carried out.
In most cases it is sufficient to program
the
VLT
®
according to items 1-10.
Quick setup
Standard motor running in constant torque application without a brake module on the frequency converter
The following settings are also used for specialised motors and parallel coupled motors, or variable torque
application or when a brake module is mounted
Item
Parameter
Description
Settings
Display
1
100
Load
For normal applications with
constant torque:
Select: “Constant torque compensated”
CT WITH COMP
For
centrifugal pumps and fans:
Select: “VT medium”
VT MODE-MED
For
centrifugal pumps and fans with heavy start:
Select: “VT Medium CT Start”
VT MED W/CT
For
synchronous motors, parallel coupled motors or specialised motors
Select: “Constant torque”
CT MODE
2
300
Brake option
If
brake option/module is used:
Select: “Applied”
APPLIED
3
Start frequency converter
This is by applying 24 V
D.C.
to terminals 18 and 27 from
terminal 12 or by using external 24 V
D.C.
voltage.
The following settings are used for local operation and start
Item
Parameter
Description
Settings
Display
1
003
Operation mode
Select: “Local”
LOCAL
2
004
Local reference
Set required output frequency using the "+" or "
−
" keys.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com