111
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
✮
= Factory setting. Text in ( ) = Display text.
The figures in [ ] are used in bus communication.
Value:
Control ready (control ready)
[0]
Unit ready (unit ready)
[1]
✭
Unit ready remote control
(UNT RDY RCTL)
[2]
Enabled (enabled no WR)
[3]
Running (running)
[4]
Running no warning
(RUNNING NO WR)
[5]
Running in range
(RUNinRANGE)
[6]
Speed = reference no warning
(RUN@REF no WR)
[7]
Alarm (alarm)
[8]
Alarm or warning (alarm/warn)
[9]
Current limit (current limit)
[10]
Out of frequency range
(OUT FRQ RGE)
[11]
Out of current range
(OUT CURR RGE)
[12]
Motor thermal overload
(mot. therm.W)
[13]
Ready and no motor
thermal overload
(ready-mot.OK)
[14]
Ready and no motor (rdy.mot.rem) [15]
Ready and no over/undervoltage
(ready + D.C. V ok)
[16]
Motor magnetized (motor mag.)
[17]
410
Relay output 04
(Relay 04)
You can use relay output 04 and relay
output 04 to indicate status and warn-
ings.
The relay is activated when the condi-
tions for the selected data values are ful-
filled.
When relay 04 is active there is connec-
tion between terminals 4 and 5.
(Make contact). [0]-[12]: See explanation in
parameter 407 [17]. See explanation in
parameter 409.
Used to determine how the frequency
converter is to follow an analogue refer-
ence signal, see graph on page 71.
Value:
✭
Linear between min. and max.
(linear)
[0]
Proportional with min. limit
(prop w/min.)
[1]
Proportional with reversing
(PROP W/REV)
[2]
411
Analogue
reference type
(Analog ref type)
412
Terminal 53
Analogue input
voltage
(Input # 53 ana)
Value:
No operation (no operation) *)
[0]
✭
0-
±
10 V (0-10 volt)
[1]
10-0 V (10-0 VDC)
[2]
2-10 V (2-10 VDC)
[3]
10-2 V (10-2 VDC)
[4]
1-5 V (1-5 VDC)
[5]
5-1 V (5-1 VDC)
[6]
Record the type of analogue input signals
to input 53 and 60. You can choose be-
tween voltage and current and whether you
want the signals to be normal or inverse.
If both inputs are used for reference signals,
the total reference signal is the sum of both.
(See p. 68). The sum is registered with a
sign.
If you are using the PID controller without
the PULSE INPUT, terminal 17 (parameter
401), one of the analogue inputs must be
used for the feedback signal.
If you are using remote current control (para.
102), one of the inputs must be used to set
current limit.
Naturally these choices block use of the
same type as reference signal.
413
Terminal 60
Analogue input
current
(Input # 60 ana)
Value:
No operation (no operation) *)
[0]
✭
0-20 mA (0-20 mA)
[1]
4-20 mA (4-20 mA)
[2]
20- 0 mA (20-0 mA)
[3]
20- 4 mA (20-4 mA)
[4]
*) If terminal 53 and/or terminal 60 are not
used, “no operation” should be selected
in parameters 412 and 413 to avoid the
risk of a reference fault.
Parameter description
4.. Inputs and outputs