Parameter
103 Motor power
0.75
1.5
2.2
4
5.5
7.5
11
15
22
30
37
45
55
75
90
110
132
160
104 Motor voltage
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
105 Motor frequency
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
107 Motor current
2
3.7
5.3
9.1
12.2
15.8
22.8
31.1
42.8
59.3
72
86.2
106.3
134.1
166.8
197.8
230
272.4
108 Motor magnetizing current
1.1
2
2.4
3.6
4.6
5.4
8.6
10.2
13.1
20
20.3
28
34.5
40.1
53.6
60.3
67.8
77.5
109 Start voltage
40
39.1
36.8
35.6
35.4
35.2
35
34.9
34.9
36.8
36.2
36.8
36.7
36.7
36.7
36.7
36.7
36.7
110 Start compensation
16
5
5
2.3
1.6
1.19
0.7
0.46
0.28
0.21 0.23.
0
0
0
0
0
0
0
111 U/F ratio
6.84
6.94
7.03
7.13
7.13
7.18
7.2
7.28
7.3
7.32
7.22
7.33
7.31
7.3
7.3
7.3
7.3
7.3
112 Slip compensation
4.86
3.8
3.2
2.6
2.08
1.72
1.24
1.14
0.84
0.74
0.52
0.56
0.52
0.36
0.32
0.28
0.26
0.24
113 Negative slip comp.
4.86
3.8
3.2
2.6
2.08
1.72
1.24
1.14
0.84
0.74
0.52
0.56
0.52
0.36
0.32
0.28
0.26
0.24
202 Max. frequency
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
209 Current limit
3.5
6.6
9
16
20.8
25.6
38.4
51.2
70.4
97.6 116.8
129
158
209
252
308
365
453
215 Ramp-up time
1
1
1
1
10
10
10
15
15
15
15
30
30
30
30
30
30
30
216 Ramp-down time
1
1
1
1
10
10
10
15
15
15
15
30
30
30
30
30
30
30
217 Alt. ramp-up time
1
1
1
1
10
10
10
15
15
15
15
30
30
30
30
30
30
30
218 Alt. ramp-down time
1
1
1
1
10
10
10
15
15
15
15
30
30
30
30
30
30
30
232 Current, min. value
0.6
1
1.2
1.8
2.3
2.7
4.3
5.1
6.6
10
10.2
14
17.3
20.1
26.8
30.2
33.9
38.8
308 D.C. brake voltage
28
25
28
21
14
13
11
12
11
21
20
20
0.0
0.0
0.0
0.0
0.0
0.0
311 Trip delay at inverter fault
2
2
2
2
9
9
9
12
12
12
12
0
0
0
0
0
0
0
3002
3003
3004
3006
3008
3011
3016
3022
3032
3042
3052
3060
3075
3100
3125
3150
3200
3250
380/41
5
V
Factory settings
Содержание VLT 3000 Series
Страница 18: ...18 MG 30 A7 02 VLT is a registered Danfoss trademark Function diagram for VLT type 3008 385 415 V Product range...
Страница 58: ...58 MG 30 A7 02 VLT is a registered Danfoss trademark EMC installation VLT 3060 3250...
Страница 62: ...62 MG 30 A7 02 VLT is a registered Danfoss trademark How the display looks in the four modes Display layout...
Страница 147: ...147 MG 30 A7 02 VLT is a registered Danfoss trademark Accessories...
Страница 156: ......