300
Brake option
(Brake option)
Value:
✭
Not applied (not applied)
[0]
Applied (applied)
[1]
The parameter is used with the brake op-
tion and brake resistor.
A higher interme-
diate circuit voltage during braking is
permitted.
Parameter description
3.. Functions and timers
301
Start frequency
(Start freq.)
Value:
0.0 - 10 Hz
✭
0.0
Insert the start frequency at which the
motor is to start (can e.g. be used on raise/
lower application).
Value:
0.0 - 1 sec.
✭
0.0
302
Start delay
(Start delay)
The VLT
®
frequency converter will start on
the start frequency (parameter 301) and
start ramping up after the start delay time
is over.
Set the time needed for high starting
torque. A high initial torque means that a
current of 2 x the current limit in parameter
209 is permitted. However, the current is
limited by the inverter’s protection limit.
Value:
0.0 - 1 sec.
✭
0.0
303
High starting torque
(HI start torq)
Function:
Select one of the 3 ramp-down functions to
prolong the ride through time at mains fail-
ure. The effect will depend on the load and
the mains voltage before failure.
Description of choices:
UNCONTROLLED STOP:
The motor will
continue running at the selected speed un-
til control trips.
RAMP-DOWN 1: The motor will start to
ramp down imme-diately (parameter 216)
until control trips.
RAMP-DOWN 2: The motor will start to
ramp down immediately (parameter 218).
Reliable regenerative operation of the
frequency converter over the ramp down 1
or 2 function requires a large inertia force
and negligible operational motor load on
the frequency converter.
Value:
✭
Uncontrolled stop (stop)
[0]
Ramp-down 1 (ramp stop)
[1]
Ramp-down 2 (alt. ramp st.)
[2]
304
Mains failure
(Power fail)
Function:
The parameter is used when the VLT
®
frequency converter is cut in on a rotating
motor (e.g. after current has been
disconnected). This function is optimal at a
4.5 kHz switching frequency. The function
may not work properly when using another
switching frequency.
Description of choices:
OK - same direction: Chosen if the motor
can only rotate in same direction on cut-in.
OK - both directions: Chosen when the
motor can only rotate in both directions on
cut-in.
Stop - before start: Selected if the motor
is to be stopped using d.c brake before
the motor is ramped up to the desired
speed. The D.C. brake time must be set in
parameter 306. The selected function is
activated in accordance with the diagram
on
p.
72.
Value:
✭
Disable (disable)
[0]
OK - same direction (same direct)
[1]
OK - both directions (both direct)
[2]
DC-brake before start
(DC-brake 1st)
[3]
305
Flying start
(Flying start)
Содержание VLT 3000 Series
Страница 18: ...18 MG 30 A7 02 VLT is a registered Danfoss trademark Function diagram for VLT type 3008 385 415 V Product range...
Страница 58: ...58 MG 30 A7 02 VLT is a registered Danfoss trademark EMC installation VLT 3060 3250...
Страница 62: ...62 MG 30 A7 02 VLT is a registered Danfoss trademark How the display looks in the four modes Display layout...
Страница 147: ...147 MG 30 A7 02 VLT is a registered Danfoss trademark Accessories...
Страница 156: ......