25
MG.30.A7.02 - VLT
®
is a registered Danfoss trademark
Mains supply 3 x 380/400/415 V
Technical data
According to international VDE and UL/CSA requirements
VLT
type
3060
3075
3100
3125
3150
3200
3250
Constant torque (CT):
Output current
I
VLT,N
[A]
86
105
139
168
205
243
302
I
VLT,MAX
[A] (60s)
129
158
209
252
308
365
453
Output
S
VLT,N
[kVA] 61.8
73
96
116
142
168
209
S
VLT,MAX
(60s)
89
109
144
175
213
253
314
Typical shaft output
P
VLT,N
[kW]
45
55
75
90
110
132
160
Quadratic torque (VT):
Output current
I
VLT,N
[A]
105
139
168
205
243
302
368
I
VLT,MAX
[A] (60s)
116
153
185
226
267
332
405
Output
S
VLT,N
[kVA]
73
96
116
142
168
209
255
Typical shaft output
P
VLT,N
[kW]
55
75
90
110
132
160
200
Max. cable cross-section
[mm
2
]
70
70
150
150
150
2x95
2x95
Max. motor cable length
[m]
300
Output voltage
U
M
[%]
0-100 of mains voltage
Output frequency
f
M
[Hz]
0-120 or 0-500, programmable
Rated motor voltage
U
M,N
[V]
380/400/415/440/460/500
Rated motor frequency
f
M,N
[Hz]
50/60/87/100
Thermal protection during operation
Integrated thermal motor protection (electronic);
thermistor to DIN 44081
Switching on output
Unlimited (frequent switching on output may result in fault message)
Ramp times
[s]
0.1 - 3600
VLT
Type
3060
3075
3100
3125
3150
3200
3250
Input current
I
L,N
[A]
84.6
103.3
138.4
167.2
201.7
241.9
307.6
I
L,MAX
(60s) [A] 129.0
158.0
209.0
252.0
308.0
365.0
453.0
Quadratic load
I
L,N
[A]
103.3
138.4
167.2
201.7
241.9
293.3
366.3
I
L,MAX
(60s) [A] 116.0
153.0
185.0
226.0
267.0
332.0
405.0
Max. cable cross-section
[mm
2
]
120.0
120.0
2 x 120 2 x 120
2 x 120
2 x 240
2 x 240
Pre-fuses
1)
[A]
150.0
150.0
250.0
250.0
300.0
450.0
500.0
Supply voltage (VDE 0160)
[V]
3 x 380/400/415/440/460/500 ±10%
Supply frequency
[Hz]
50/60
Power factor / cos.
ϕ
1
0.9/1.0
Efficiency
0,96 at 100% load
Switching on input
times/min.
1
VLT type
3060
3075
3100
3125
3150
3200
3250
Weight (kg)
IP 21
147
147
211
211
220
306
306
IP 54
147
147
211
211
220
306
306
Power loss at max. load CT [W]
Front
423
529
713
910
1091
1503
1812
Heat sink
859
1074
1447
1847
2216
3051
3679
Power loss at max. load VT [W]
Front
529
713
910
1091
1503
1812
2209
Heat sink
1074
1447
1847
2216
3051
3679
4485
Enclosure
IP 21 / IP 54
NEMA 1/12
Vibration test
[g]
0.7
Relative humidity
[%]
VDE 0160 5.2.1.2.
Ambient temperature
[°C]
-10
→
+40 operation at full load (VT) -10
→
+45 (CT)
2)
(to VDE 0160)
[°C]
-30/25
→
+65/70 in storage/transport
Frequency converter protection
Protection against earthing and short-circuiting
EMC standards
Emission
EN 55011, EN 55014
(See section “EMC test results”)
Immunity
EN 50082-2, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4,
IEC 1000-4-5, VDE 0160
1) Bussman rapid type JJS integrated.
2) In the range -10 to 0°C, the equipment can start and run; however, the display values and certain operating characteristics will not fulfil the
specifications.
Содержание VLT 3000 Series
Страница 18: ...18 MG 30 A7 02 VLT is a registered Danfoss trademark Function diagram for VLT type 3008 385 415 V Product range...
Страница 58: ...58 MG 30 A7 02 VLT is a registered Danfoss trademark EMC installation VLT 3060 3250...
Страница 62: ...62 MG 30 A7 02 VLT is a registered Danfoss trademark How the display looks in the four modes Display layout...
Страница 147: ...147 MG 30 A7 02 VLT is a registered Danfoss trademark Accessories...
Страница 156: ......