Index Monitored value
Unit
ID Description
V1.1
Output frequency
Hz
1
The output frequency to the motor
V1.2
Frequency reference
Hz
25 The frequency reference to motor control
V1.3
Motor speed
rpm
2
The actual speed of the motor in rpm
V1.4
Motor current
A
3
Measured motor current
V1.5
Motor torque
%
4
The calculated shaft torque
V1.6
Motor power
%
5
The calculated motor shaft power in percentage
V1.7
Motor voltage
V
6
The output voltage to the motor
V1.8
DC link voltage
V
7
The measured voltage in the DC-link of the drive
V1.9
Unit temperature
°C
8
The heat sink temperature in Celsius or Fahrenheit
V1.10
Motor temperature
%
9
The calculated motor temperature in percentage of the nominal temperature. See
VACON
®
All in One Application Manual.
V1.11
Analog input 1
V/mA 13 AI1
(1)
V1.12
Analog input 2
V/mA 14 AI2
(1)
V1.13
DIN 1, 2, 3
15 Shows the status of the digital inputs 1–3
V1.14
DIN 4, 5, 6
16 Shows the status of the digital inputs 4–6
V1.15
DO1, RO1, RO2
17 Shows the status of the digital and relay outputs 1–3
V1.16
Analog I
out
mA
26 AO1
V1.17
Multimonitoring items
Shows 3 monitored values to select from. See
8.7.6.9 Enabling/Disabling the Change
1
If the AC drive only has +24 V supply (for control board power-up), this value is not reliable.
See VACON
®
All in One Application Manual for more monitored values.
8.3 Using the Parameter Menu (M2)
8.3.1 Finding the Parameter
Context:
Use these instructions to find the parameter to edit.
Using the Control Panel
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 57
Danfoss A/S © 2019.11
Содержание VACON NXP FI10
Страница 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Страница 2: ......
Страница 170: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 170 Danfoss A S 2019 11...
Страница 171: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 171 Danfoss A S 2019 11...