Enclosure size
(1)
Drive type
I
L
[A]
Supply cable Cu [mm
2
]
Motor cable [mm
2
]
(2)
FI13
NXI_1150 5
1150
5×40
(4)
Cu: 4×(3×240+170)
Al: 6× (3×185Al+57Cu)
NXI_1300 5
1300
5×40
(4)
Cu: 6×(3×150+70)
Al: 6× (3×240Al+72 Cu)
NXI_1450 5
1450
6×40
(4)
Cu: 6×(3×185+95)
Al: 6× (3×240Al+72 Cu)
FI14
(5)
NXI_1770 5
1770
5×40
(4)
Cu: 2× 4×(3×240+170)
Al: 2× 6× (3×185Al+57Cu)
NXI_2150 5
2150
5×40
(4)
Cu: 2× 6×(3×150+70)
Al: 2× 6× (3×240Al+72 Cu)
NXI_2700 5
2700
6×40
(4)
Cu: 2× 6×(3×185+95)
Al: 2× 6× (3×240Al+72 Cu)
1
Table valid for protection rating IP20 cabinets.
2
EN 60204-1, IEC 60364-5-2/2001; PVC insulation; 40 °C ambient temperature; 70 °C surface temperature
3
Flexible conductor. Min. temperature endurance for isolation 70°C
4
Copper Busbar
5
The modules require symmetrical parallel cable with min length 40 m or dU/dt- or sine filter.
12.4.3 Terminal Sizes for 465–800 V DC (380–500 V AC)
Table 20: Terminal Sizes for 465–800 V DC (380–500 V AC)
Enclosure size
Drive type
I
L
[A]
DC supply terminal
Motor terminal
FI9
NXI_0168 5
170
13
8x
40
16
35
e3
0b
h4
46
.1
0
PE: M8 × 25
13
6x
40
17
38
e3
0b
h4
48
.1
0
NXI_0205 5
205
NXI_0261 5
261
NXI_0300 5
300
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909
118 | Danfoss A/S © 2019.11
Содержание VACON NXP FI10
Страница 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Страница 2: ......
Страница 170: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 170 Danfoss A S 2019 11...
Страница 171: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 171 Danfoss A S 2019 11...