I = I
n
*(1- (h-2000)/100*0.5/100)
Where
I = Current rating at high altitude
I
n
= Rated current of a fuse
h = Altitude in meters
A Loadability, %
C Loadability
B Altitude, meters
Illustration 7: Loadability in High Altitudes
5.2 Cooling Requirements
5.2.1 General Cooling Requirements
The AC drive produces heat in operation. The fan moves air and decreases the temperature of the drive. Make sure that there is
sufficiently free space around the drive.
Make sure that the temperature of the cooling air does not go above the maximum ambient operating temperature or below the
minimum ambient operating temperature of the drive.
5.2.2 Cooling of FI9 to FI14
If many AC drives are installed above each other, the necessary free space is 2 x B
2
(see
). Make also sure that the outlet air
from the lower drive goes to a different direction than the air intake of the top drive.
Mounting the Unit
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 29
Danfoss A/S © 2019.11
Содержание VACON NXP FI10
Страница 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Страница 2: ......
Страница 170: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 170 Danfoss A S 2019 11...
Страница 171: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 171 Danfoss A S 2019 11...