Procedure
1. In the
System info
submenu, find the
Expander boards
page (
6.8.6
) with the Browser buttons.
2. To go to the
Expander boards
page, push the Menu button Right.
3. To select the board, use the Browser buttons.
If no board is connected to the slot, the display shows
no board
.
If a board is connected to a slot but there is no connection, the display shows
no conn.
.
4. To see the status of the board, push the Menu button Right.
5. To see the program version of the board, push the Browser button Up or Down.
8.7.9.10 Debug Menu (S6.8.7)
The Debug menu is for advanced users and application designers. Speak to the factory to get instructions, if it is necessary.
8.8 Using the Expander Board Menu
8.8.1 Expander Board Menu
The
Expander board
menu, that is, the menu for option board information, allows to:
•
see which option boards are connected to the control board
•
find and edit the option board parameters.
Table 15: Option Board Parameters (Board OPTA1)
Page
Parameter
Min
Max
Default
Cust
Selections
P7.1.1.1
AI1 mode
1
5
3
1 = 0–20 mA
2 = 4–20 mA
3 = 0–10 V
4 = 2–10 V
5 = –10…+10 V
P7.1.1.2
AI2 mode
1
5
1
See P7.1.1.1
P7.1.1.3
AO1 mode
1
4
1
1 = 0–20 mA
2 = 4–20 mA
3 = 0–10 V
4 = 2–10 V
8.8.2 Examining the Connected Option Boards
Context:
Use these instructions to examine the connected option boards.
Using the Control Panel
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 83
Danfoss A/S © 2019.11
Содержание VACON NXP FI10
Страница 1: ...Operating Guide VACON NXI Inverters FI9 FI14...
Страница 2: ......
Страница 170: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 170 Danfoss A S 2019 11...
Страница 171: ...Operating Guide VACON NXI Inverters FI9 FI14 AQ304441431479en 000101 DPD00909 171 Danfoss A S 2019 11...