Enclosure size
(1)
Drive type
I
L
[A]
Supply cable Cu [mm
2
]
Motor cable [mm
2
]
(2)
FI12
(5)
NXI_0460 6
460
5×40
(4)
Cu: 2×(3×150+70)
Al: 2×(3×240Al+72Cu)
NXI_0502 6
502
5×40
(4)
Cu: 2×(3×185+95)
Al: 2×(3×300Al+88 Cu)
NXI_0590 6
590
5×40
(4)
Cu: 2×(3×240+120)
Al: 4×(3×120Al+41Cu)
NXI_0650 6
650
5×40
(4)
Cu: 4×(3×95+50)
Al: 4×(3×150Al+41Cu)
NXI_0750 6
750
5×40
(4)
Cu: 4×(3×120+70)
Al: 4×(3×150Al+41Cu)
NXI_0820 6
820
5×40
(4)
Cu: 4×(3×150+70)
Al: 4×(3×185Al+57Cu)
FI13
NXI_0920 6
920
5×40
(4)
Cu: 4x(3x150+70)
Al: 4x(3x240+72Cu)
NXI_1030 6
1030
5×40
(4)
Cu: 4x(3x185+95)
Al: 5x(3x185+57Cu)
NXI_1180 6
1180
5×40
(4)
Cu: 5x(3x185+95)
Al: 6x(3x185+72Cu)
FI14
(5)
NXI_1500 6
1500
5×40
(4)
Cu: 2×4×(3×120+70)
Al: 2×4×(3×150Al+41Cu)
NXI_1900 6
1900
5×40
(4)
Cu: 2×4x(3x185+95)
Al: 2×5x(3x185+57Cu)
NXI_2250 6
2250
5×40
(4)
Cu: 2×5x(3x185+95)
Al: 2×6x(3x185+72Cu)
1
Table valid for protection rating IP20 cabinets.
2
EN 60204-1, IEC 60364-5-2/2001; PVC insulation; 40 °C ambient temperature; 70 °C surface temperature
3
Flexible conductor. Min. temperature endurance for isolation 70°C
4
Copper Busbar
5
The modules require symmetrical parallel cable with min length 40 m or dU/dt- or sine filter.
Specifications
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909| 121
Danfoss A/S © 2019.11