NOTICE
MAINS CONNECTION DEVICE
If the AC drive is used as a part of a machine, the machine manufacturer must supply a mains disconnection device (refer to EN
60204-1).
NOTICE
MALFUNCTION OF FAULT CURRENT PROTECTIVE SWITCHES
Because there are high capacitive currents in the AC drive, it is possible that the fault current protective switches do not
operate correctly.
NOTICE
VOLTAGE WITHSTAND TESTS
Doing voltage withstand tests can damage the drive.
-
Do not do voltage withstand tests on the AC drive. The manufacturer has already done the tests.
Safety
Operating Guide | VACON® NXI Inverters FI9-FI14
AQ304441431479en-000101 / DPD00909
14 | Danfoss A/S © 2019.11