e
3
0
b
g
0
8
8
.1
0
5.
Connect the cables. See the correct tightening torques in
12.6 Tightening Torques of the Terminals
.
•
Connect the phase conductors of the DC supply cable and of the motor cable, and the conductors of the brake resistor cable
into the correct terminals.
6.
Make sure to connect the grounding conductor to the motor and the terminals that are identified with the grounding symbol.
•
If a double grounding is necessary, use the grounding terminal below the drive. Use an M5 screw and tighten it to 2.0 Nm or
17.7 lb-in.
e
3
0
b
g
0
9
3
.1
0
7.
12.5 Tightening Torques for Cover Screws
. Attach the grounding clamps for control cable with 3 pieces of
M4x16 screws delivered in the accessories bag. Use these clamps to ground the control cables.
Electrical Installation
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
54 | Danfoss A/S © 2019.07
Содержание VACON NX FI6
Страница 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Страница 2: ......
Страница 164: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 164 Danfoss A S 2019 07...
Страница 165: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 165 Danfoss A S 2019 07...