Troubleshooting
•
Do a check of the encoder connection.
•
PMS motor has exceeded the pull-out torque.
12.10.131 Fault 62 - Run disable
Cause
Run enable signal is low.
Troubleshooting
Do a check of the reason for the Run enable signal.
12.10.132 Fault 63 - Quick stop
Cause
Command for quick stop received from digital input or fieldbus.
This fault is type A fault (Alarm).
Troubleshooting
Reset the fault.
12.10.133 Fault 64 - Input switch open
Cause
Drive input switch is open.
This fault is type A fault (Alarm)
Troubleshooting
Do a check of the main power switch of the drive.
12.10.134 Fault 65 - Measured Temperature
Cause
Shows temperature measurement fault for option board OPTBH or OPTB8.
•
Temperature exceeded set limit.
•
Sensor disconnected.
•
Short circuit.