3
The rubber grommets GD21 (FR7/FI7 IP54/UL Type 12),
3 pieces / (FR8/FI8), 6 pieces
Illustration 7: Contents of the Accessories Bag for FR7-FR8/FI7-FI8
4.2 Storing the Product
Context:
If the product has to be stored before installing it, follow these instructions.
Procedure
1.
If the AC drive must be stored before using it, make sure that the ambient conditions agree to the following:
•
Storage temperature: -40…+70° C (-40...+158° F)
•
Relative humidity: 0–95%, no condensation
2.
If the AC drive must be kept in storage for a long time, connect the power to the AC drive each year. Keep the power on for a
minimum of 2 hours.
3.
If the storage time is more than 12 months, charge the electrolytic DC capacitors with caution. To reform the capacitors, obey the
instructions in
.
We do not recommend a long storage time.
4.3 Lifting the Product
Context:
To get information on how to lift the AC drive safely, speak to the factory or the local distributor.
Prerequisites:
The weights of AC drives of different enclosure sizes are different. It can be necessary to use a lifting device to move the drive from its
package.
Procedure
1.
Check the weight of the inverter, see
2.
To lift the AC drives larger than FR7/FI7 out of the package, use a jib crane.
3.
After lifting the drive, check for signs of damage on the drive.
4.4 Using the Product Modified Label
Context:
In the accessories bag, there is also a "product modified" label. The function of the label is to tell the service personnel about the
changes that are made in the AC drive.
Receiving the Delivery
Operating Guide | VACON® NX Inverters FI4-FI8
AQ299433367205en-000101 / DPD00908
28 | Danfoss A/S © 2019.07
Содержание VACON NX FI6
Страница 1: ...Operating Guide VACON NX Inverters FI4 FI8...
Страница 2: ......
Страница 164: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 164 Danfoss A S 2019 07...
Страница 165: ...Operating Guide VACON NX Inverters FI4 FI8 AQ299433367205en 000101 DPD00908 165 Danfoss A S 2019 07...