Cause
Check
Corrective action
Incorrect signal voltage
Check voltage levels at solenoid plug
Proportional operation - Refer to
Troubleshooting Considerations
Udc: Supply voltage (100%)
Us: Supply signal voltage (25-50-75%)
Ground: Live or ground connection
On-Off Operation
Udc: Supply voltage if selected
Us: Supply voltage if selected
Ground: Live or ground connection
Solenoid valve faulty PVHC
Check coil resistance
Check data for resistance
Insufficient pilot supply
Check pilot pressure - 10-15 bar [145-218 psi]/PVHC 25 bar [360
psi]
Replace
Main spool position feedback
transducer signal incorrect
Test oil for contamination and or water content
If oil contamination is too high, flush hydraulic
system or replace oil if necessary. If problem
persists change PVE
Incorrect PVE connections
Check that the proportional remote electrical controller has not
been connected to an ON-OFF PVEO solenoid
Connect wires correctly
Hydraulic (remote) pilot control pressure
Cause
Check
Corrective action
Insufficient pilot pressure
Check pilot oil pressure 5-15 bar [72-220 psi] delta between A and
B port on remote
PVG32: 5-15 Bar [72-217 PSI]
Insufficient pilot oil supply
Check pilot oil flow rate is adequate
Pilot flow should be 1.0 L/min [0.264 GPM] per section
Check pilot lines for blockage
Remove blockage
Air in pilot line
Check for trapped air in pilot lines
Bleed air from pilot lines at PVH
Pilot lines incorrectly sized
Check pressure drop
Check and reduce length or pilot lines
Increase diameter of pilot lines
Use steel tube for long pilot line runs
Hydraulic remote pilot operator
faulty
Check operation of hydraulic remote pilot controller
Repair or replace
Check supply pressure to hydraulic remote controller - minimum
25 bar [360 psi]
Repair or replace
Check and inspect movement of pressure control valve in
hydraulic controller
Repair per manufacturers procedure, or
replace
Check operation of remote hydraulic controller
Clean and/or repair as necessary
Service Manual
PVG 32 Proportional Valve Group
System Troubleshooting
©
Danfoss | February 2017
11039167 | AX00000031en-US0301 | 19