Instructions
118A2176C - AN37261865152501-010301 | 7
© Danfoss | Climate Solutions | 2022.02
17 - Dual Pressure switch - Factory settings
18 - Dual Pressure switch - Refrigerant setting
Refrigerants
High pressure settings (bar (g))
Low pressure settings (bar (g))
ON
OFF
ON
OFF
R404A/R507/R407A/R407F/R448A/R449A/R452A,R454C, R455A
23
27
2
1
R134a/R513A
13
17
2
1
Refrigerants
High pressure settings (bar (g))
Low pressure settings (bar (g))
ON
OFF
ON
OFF
R134a, R513A, R1234yf
14
17
2
1
R404A/R507, R452A
24
27
2
1
R454C
19
23
2
1
R455A
21
25
2
1
R448A/R449A
22
26
2
1
19 - Fan speed controller setting - AC Fan Motor (B1 & B2 Chassis models)
20 - Fan speed controller setting EC Fan Motor (B3, W09)
FSC type
Fan speed Controller
Spare part number
Refrigerant
letter
For Refrigerant
Factory
setting
Action required*
XGE-2C
061H3144
S
R134a/R513A/R1234yf
8 bar
360°=1 turn = Approx 0.8 bar
(Clockwise rotation =
Increase pressure setting,
Counter clockwise rotation =
Decrease pressure setting)
061H3248
V
R404A/R452A/R507
15 bar
X
R404A/R507/ R407A/R407F/R448A/
R449A/R452A (Except R134a and
R513A)
15 bar
T
R404A / R507, R455A, R454C, R448A/
R449A, R452A
15 bar
I
R404A / R507, R407A, R407F, R448A,
R449A, R452A, R454C, R455A (Except
R134a and R513A)
15 bar
Rotate the screw by 9 turns in counter
clockwise direction to reach 8 bar
FSC type
Fan speed Controller
Spare part number
Refrigerant
letter
For Refrigerant
Factory
setting
Recommended
setting
Action required*
XGE-4C
061H3246
I
R134a/R513A
15 bar
10 bar
Rotate the screw by 3 turns in counter
clockwise direction to reach 10 bar
R404A / R507, R407A,
R407F, R448A, R449A,
R452A, R454C, R455A
15 bar
15 bar
* Installer can set the required setting based on application.
* Installer can set the required setting based on application.
Clockwise Direction = Increase the pressure setting.
Counter Clockwise Direction = Decrease the pressure setting