Instructions
© Danfoss | Climate Solutions | 2022.02
50 | AN37261865152501-010301 - 118A2176C
OP - MSIM 034 ML W05 G
1 2 3 4
5
6
7
8
1 Application
M = MBP
L = LBP
2 Package
Condensing unit family: S = Slim Pack
3 Refrigerant
T = R404A/R507, R455A, R454C, R448A/R449A, R452A
S = R134a, R513A, R1234yf
V = R454C, R455A, R452A, R404A/R507
X = R404A / R507, R134a, R407A, R407F, R448A, R513A, R449A,
R452A
I = R404A / R507, R134a, R407A, R407F, R448A, R513A, R449A,
R452A, R454C, R455A
4 Condenser
M = Microchannel heat condenser
5 Swept volume
Displacement in cm
3:
Example 034 = 34 cm
3
6 Compressor platform
DP/DX/DS = Fixed speed Reciprocating compressor
MP/MX/MS = Fixed speed Reciprocating compressor,
ML = Scroll compressor
7 Version
W05: Optyma™ Slim Pack standard version (see Version table)
W09: Optyma™ Slim Pack with Fan speed Controller
8 Voltage code
G = 230V/1-phase compressor & fan
E = 400V/3-phase compressor & 230V/1-phase fan
Optyma™
Slim Pack
W05*
W09*
Condensing unit :IP level
IP54
IP54
Refrigerant
Group 1 / Group 2 Group 1 / Group 2
Compressor technology
Reciprocating / Scroll Reciprocating / Scroll
Control box (pre-wired E-panel)
yes
yes
Microchannel condenser
yes
yes
Fan speed controller
-
yes
Main switch (circuit breaker)
-
yes
Filter drier (flare connections)
yes
yes
Sight glass
yes
yes
Crankcase heater
yes
yes
HP/LP adjustable pressostat
Auto/Manual reset
mode
Auto/Manual reset
mode
Access door(s)
yes for E-Box
yes for E-Box
Acoustic insulation
Provided as accessory.
Not supplied with unit.
Discharge gas thermostat
(Provision)
yes
yes
HP/LP Alarm (Provision)
yes
yes
Electrical Box design
IP54
IP54
Adjustable time delay
(Compressor)
yes
yes
Pressure Relief Valve**
-
-
Version control
Designation system for the
Optyma
™ Slim Pack range
* Compatible with A2L refrigerant
** Accessory (Not factory mounted)
N
O
L
M
L
L
[mm]
M
[mm]
N
[mm]
O
[mm]
250
50
550
550
Picture 1 : Minimum mounting distances
Annex - A
Technical data (English)
Address - Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB
Імпортер:ТОВ з іі "Данфосс ТОВ" 04080, Київ 80, п/с 168, Україна
Danfoss A/S, 6430 Nordborg, Denmark
Fluid Group
PED Category
Application
PT
TS
HP Switch Pressure
Year of Mfg.
MBP
1 & 2
II
32 bar
31 bar
2021
IP54
Voltage
LRA
MCC
RLA
400V~3N~50Hz
60 A
14 A
8.3 A
A2L
Refrigerant
Only for Norway
089
0045
0879
A
B
C
D
E
F
G
H
I
J
K
OP-MSXM108MLW05E
114X7072
PS
HP
PS
LP
o
C
V Setting
-1/32 bar
-1/21.5 bar
-30/ 63
34.5 bar
L
PR
* For exact values please refer name plate in unit
Name plate
A
: Model
B
: Code number
C
: Serial Number and bar code
D
: EAN number
E
: Refrigerant
F
: PED Category
G
: Application, Ingress Protection
H
: Maximum Allowable Pressure (HP
side)
I
: Maximum Allowable Pressure (LP
side)
J
: Test Pressure
K
: Maximum allowable Design
Temperature
L
: Pressure Relief Valve set pressure