MCO 305 Design Guide
__ Parameter Reference __
¾
default setting
[ ]
value for use in communication via serial communication port
206
MG.33.L4.02 – VLT
®
is a registered Danfoss trademark
33-5* I/O Configuration
There is one parameter per input and output. One
function assigned to each input and output via this
parameter.
Digital Input Functions
Digital input function
Select
Terminal
¾
No function
[0]
X57, X59/7,8*
Home
switch
'no'
[1] X57,
X59/7,8*
Home
switch
'nc'
[2] X57,
X59/7,8*
Negative end switch 'no'
[3] X57,
X59/7,8*
Negative end switch 'nc'
[4] X57,
X59/7,8*
Positive end switch 'no'
[5] X57,
X59/7,8*
Positive end switch 'nc'
[6] X57,
X59/7,8*
Error clear 'no'
[7] X57,
X59/7,8*
Error clear 'nc'
[8] X57,
X59/7,8*
Break program exe 'no'
[9]
X57, X59/7,8*
Break program exe 'nc'
[10] X57,
X59/7,8*
Continue program exe 'no'
[11] X57,
X59/7,8*
Continue program exe 'nc'
[12] X57,
X59/7,8*
Start program exe 'no'
[13] X57,
X59/7,8*
Start program exe 'nc'
[14] X57,
X59/7,8*
Program
select
[15] X57,
X59/7,8*
X57 = all
*) X59/7,8 only if par. 33-60 IOMODE is set to [0].
You can program all digital inputs 1 – 10 (12) to
these functions:
No function [0]:
No reaction on signals from
the input_n.
Home switch no [1]:
Defines digital input_n of
MCO 305 as home switch. Behavior after
reaching see HOME_TYPE.
Home switch nc [2]:
Defines digital input_n
as home switch inverse. Behavior after
reaching, see HOME_TYPE.
Negative end switch no [3]:
Defines digital
input_n as the negative end switch.
Negative end switch nc [4]:
Defines digital
input_n as the negative end switch inverse.
Positive end switch no [5]:
Defines digital
input_n as the positive limit switch.
Positive end switch nc [6]:
Defines digital
input_n as the positive limit switch inverse.
Error clear no [7]:
Defines digital input_n to
be used to clear an error.
Error clear nc [8]:
Defines digital input_n to
be used to clear an error.
Break program exe no [9]:
Defines digital
input_n to be used to react and abort a program
immediately, when activated. Such a program
can be continued with CONTINUE.
Break program exe nc [10]:
Defines digital
input_n to be used to react and abort a program
immediately, when activated. Such a program
can be continued with CONTINUE.
Continue program exe no [11]:
Defines
digital input_n to be used to continue aborted
programs.
Continue program exe nc [12]:
Defines
digital input_n to be used to continue aborted
programs.
Start program exe no [13]:
Defines digital
input_n to be used to define type of program
start.
If the input_n is set to [13], the Autostart pro-
gram is executed at first and the program waits
until input_n will be active. This is then evalua-
ted relevant to the program selection in order to
determine the number of the program to be run.
If no input for the program start is set, the pro-
gram with auto identification will be started.
Start program exe nc [14]:
Defines digital
input_n to be used to define the type of
program start. If the input_n is set to [14], the
Autostart program is executed at first and the
program waits until input_n will be active. This
is then evaluated relevant to the program selec-
tion in order to determine the number of the
program to be run.
If no input for the program start is set, the pro-
gram with auto identification will be started.
Program select [15]:
Defines digital input_n
to be used for a program selection. If input_n is
set to [15] then this parameter indicates the
input number starting at which the inputs for
the
Program Selection
are used. This includes all
numbers up to I_FUNCTION_14.