Design Guide | APP and iSave overload protection
60
180R9357 | AQ265943679828en-00100
2
IOM iSave 50 - 70 | 0
3
.202
3
3.
Standard preferred
settings
3.1 VLT FC 202 and VLT FC 302
For detailed information on how to program a
VLT FC 202 or FC 302 we refer to the “Program-
ming Guide VLT Aqua Drive FC 202 and FC 302”.
vlt-drives.danfoss.com
To calculate setting for parameter 4-16 and 4-18
please contact Danfoss.
Programming VLT:
Parameter 0-01
“Language”
Set language
Parameter 0-02
“Motor speed unit”
Set to rpm
Parameter 0-20
“LCD Display”
Choose rom, Amp, kW, Hz, Torque
Parameter 1-03
“Torque characteristic”
Set to 0 (Constant torque)
Parameter 1-06
“Clockwise direction”
Set to inverse (Clockwise)
Parameter 1-20
“Motor power kW”
According to motor name plate
Parameter 1-22
“Motor voltage”
According to motor name plate
Parameter 1-23
“Motor frequency”
According to motor name plate
Parameter 1-24
“Motor current”
According to motor name plate
Parameter 1-25
“Motor nominel speed”
Rpm according to name plate
Parameter 1-29
“Automatic motor adaption
AMA”
Run full AMA. (Remember to fuse termi-
nals 12 and 27. Push hand on. Remove fuse
after AMA)
Parameter 1-71
“Start delay”
Set in sec. (See chapter 5.3)
Parameter 1-72
“Start function”
Set to 0. (DC hold/delay/time)
Parameter 2-00
“DC hold current”
Set in % (please contact Danfoss or see
chapter 5.2 for iSave)
Parameter 3-02
“Minimum reference”
Set to 0
Parameter 3-03
“Maximum reference”
Set needed rpm. For application
Parameter 3-41
“Ramp 1. Ramp up time”
Motor ramp up time.
Pump: 10-60 sec. = 1 barg/sec.
iSave: 10.15 sec.
Parameter 3-42
“Ramp 1. Ramp down time”
Motor ramp down time.
Pump: 10-60 sec. = 1 barg/sec.
iSave: 10-15 sec.
Parameter 4-11
“Motor speed low limit”
Set low limit [rpm] for product according
to chapter 5
Parameter 4-13
“Motor speed high limit”
Set max. limit [rpm] for product according
to chapter 5
Parameter 4-19
“Max. output frequency”
[Hz] Set max. output for product
Torque limit
Parameter 4-16
“Torque limit motor mode”
Set in [%] (please contact Danfoss or see
chapter 5.2 for iSave)
Parameter 14-25
“Trip delay at torque limit”
Set to 30 sec.
Current limit
Parameter 4-18
“Current limit”
Set in [%] (Par. 4-18 must always be larger
or equal to Par. 4-16), (please contact
Danfoss or see chapter 5.2 for iSave)
Содержание iSave 50
Страница 20: ...Operating guide iSave 50 70 20 180R9357 AQ265943679828en 001002 IOM iSave 50 70 03 2023...
Страница 23: ...Data sheet iSave Energy Recovery Device iSave 50 iSave 70 hpp danfoss com...
Страница 45: ...Design guide iSave Energy Recovery Device Start and stop of the SWRO with iSave hpp danfoss com...
Страница 50: ...Danfoss DCS im 2020 01 180R9213 521B1164 DKCFN PI 003 F8 02 50...
Страница 51: ...Design guide Energy Recovery Device iSave Membrane cleaning of RO system hpp danfoss com...
Страница 56: ...Danfoss DCS im 2017 09 521B1165 DKCFN PI 00 G6 02 56...
Страница 57: ...ro solutions com Design Guide APP pumps and iSave overload protection hpp danfoss com...
Страница 65: ...Design Guide APP and iSave overload protection 65 180R9357 AQ265943679828en 001002 IOM iSave 50 70 03 2023...
Страница 66: ...Danfoss DCS im 2018 08 180R9372 521B1412 DKCFN PI 003 O2 02 66...
Страница 74: ...Danfoss DCS im 2019 05 180R9084 521B0540 DKCFN PI 000 D7 02 74...
Страница 75: ...Parts list Energy recovery device iSave 50 70 hpp danfoss com...
Страница 86: ...86 Danfoss DCS im 2021 03 180R9392_AX299849991270en 000701...
Страница 87: ...M a n u a l Electric Motors Motor Manual hoyermotors com...
Страница 91: ...91 180R9357 AQ265943679828en 001002 IOM iSave 50 70 03 2023...