Table 18: General Connectivity Settings for Active Front End
(continued)
Menu index
Parameter
Parameter number
Value
Description
2.9.8.6
Fieldbus Watchdog
Delay
5245
0.00–3000 s (Default:
5.00 s)
Set a delay time for af-
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value.
2.9.8.7
Fieldbus Watchdog
Start Delay
5246
0.00–3000 s (Default:
30.00 s)
Set a delay time for af-
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value. This time applies
only immediately after
powering the control
unit of the drive.
Table 19: Event Descriptions for Active Front End
Value
Description
Info
The event is logged in the event log.
Warning
The drive issues a warning.
Fault
A fault is issued, and the modulation is stopped
Fault, open MCB
A fault is issued, the modulation is stopped, and the MCB is opened, if controlled by the converter.
34
| Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A
Operating Guide | iC7-Marine PROFINET