Operating Guide | iC7-Marine PROFINET
4.5
General Connectivity Settings
4.5.1
Propulsion & Machinery Application Connectivity Settings
Table 16: General Connectivity Settings for Propulsion & Machinery
Menu index
Parameter
Parameter number
Value
Description
2.8.4.1
Fieldbus profile
1301
• iC Generic Profile
(Default, not
supported for
PROFINET.)
• iC Speed Profile
• PROFIdrive Standard
telegram 1
Select the fieldbus pro-
file. The selection af-
fects the interpretation
of the control word and
status word.
2.12.13.1
Fieldbus Fault Response
1303
• Info (default)
• Warning
• Fault, Ramp to Coast
• Fault, coast
See
for descrip-
tions of the events.
Select the behavior
when a fieldbus fault,
for example loss of I/O
connection occurs.
2.12.13.2
Process Data Timeout
Response
1341
• Info (default)
• Warning
• Fault, Ramp to Coast
• Fault, Coast
See
for descrip-
tions of the events.
Select the response in
case there is no fieldbus
connection.
2.12.13.3
Process Data Timeout
Time
1340
0.05–18000 s (Default
value: 1.00 s)
Set the timeout time. If
process data is not re-
ceived within the time
set, a process data time-
out is triggered.
2.12.13.4
Fieldbus Watchdog
Response
5244
• No response (default)
• Warning
• Fault, Ramp to Coast
• Fault, Coast
See
for descrip-
tions of the events.
Select the response
in case the fieldbus
watchdog bit (bit 11)
has not changed its
value within the specific
watchdog delay time.
This is only available
with the iC Generic pro-
file.
2.12.13.5
Fieldbus Watchdog
Delay
5245
0.00–3000 s
(Default: 5.00 s)
Set a delay time for af-
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value.
Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A |
31