Operating Guide | iC7-Marine PROFINET
3.5.3
Cable Routing
For more information on cabling, refer to the product-specific design guide and installation guide included in the shipment.
NOTICE
EMC INTERFERENCE
Failure to isolate fieldbus communication, motor, and brake resistor cables can result in unintended behavior or reduced
performance.
l
Use shielded cables for motor and control wiring, and separate cables for fieldbus communication, motor wiring, and brake
resistor.
l
A minimum of 200 mm (7.9 in) clearance between power, motor, and control cables is required. For power sizes above 315 kW
(450 hp), increase the minimum distance to 500 mm (20 in).
NOTICE
CABLE ROUTING
l
When the fieldbus cable intersects a motor cable or a brake resistor cable, ensure that the cables intersect at an angle of 90°.
e30bl407.10
3
2
1
Figure 10: Cable Routing
1
Fieldbus cable
2
90° intersection
3
≥200 mm (7.9 in) (≥ 500 mm (20 in) for power sizes >315
kW (450 hp))