Table 16: General Connectivity Settings for Propulsion & Machinery
(continued)
Menu index
Parameter
Parameter number
Value
Description
2.12.13.6
Fieldbus Watchdog
Start Delay
5246
0.00–3000 s
(Default: 30.00 s)
Set a delay time for af-
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value. This time applies
only immediately after
powering the control
unit of the drive.
2.12.13.7
FB Monitoring Ctrl.
Place Dependency
1338
• Disabled
• Enabled
Set the control place
dependency for
Fieldbus Fault
,
Process
Data Timeout
, and
Fieldbus Watchdog
.
When enabled, these
functions are active
only in the fieldbus
control place. When
disabled, these
functions are active
regardless of the
control place.
Table 17: Event Descriptions for Propulsion & Machinery
Value
Description
Info
The event is logged in the event log.
Warning
The drive issues a warning.
Fault, Ramp to Coast
The drive issues a fault, ramps down, and coasts.
Fault, Coast
The drive issues a fault and coasts the motor.
32
| Danfoss Drives Oy © 2024.04 AQ481922043454en-000101 / 172K4282A
Operating Guide | iC7-Marine PROFINET