Enclosure
size
Power [kW]
Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A1
0.25-1.5
gG-10
gG-25
PKZM0-16
16
A2
0.25-2.2
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-25
PKZM0-25
25
A3
3.0-3.7
gG-16 (3)
gG-20 (3.7)
gG-32
PKZM0-25
25
B3
5.5
gG-25
gG-63
PKZM4-50
50
B4
7.5-15
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-125
NZMB1-A100
100
C3
18.5-22
gG-80 (18.5)
aR-125 (22)
gG-150 (18.5)
aR-160 (22)
NZMB2-A200
150
C4
30-37
aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250
250
A4
0.25-2.2
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-32
PKZM0-25
25
A5
0.25-3.7
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-32
PKZM0-25
25
B1
5.5-7.5
gG-25 (5.5)
gG-32 (7.5)
gG-80
PKZM4-63
63
B2
11
gG-50
gG-100
NZMB1-A100
100
C1
15-22
gG-63 (15)
gG-80 (18.5)
gG-100 (22)
gG-160 (15-18.5)
aR-160 (22)
NZMB2-A200
160
C2
30-37
aR-160 (30)
aR-200 (37)
aR-200 (30)
aR-250 (37)
NZMB2-A250
250
Table 10.14 200-240 V, Frame Sizes A, B and C
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark
83
10
10
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions VLT AutomationDrive FC 300 0 25 75 kW...
Страница 2: ......
Страница 4: ...Safety VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark...
Страница 99: ...Index VLT AutomationDrive Operating Instructions MG33AM02 VLT is a registered Danfoss trademark 95...
Страница 100: ...www danfoss com drives MG33AM02 130R0300 MG33AM02 Rev 2012 11 02...